Range of lever operated spherical valves with brass bodies (nickel plated), chrome plated brass balls, and EPDM ‘O’-rings. Compression connections are for use with copper pipe (manufactured to EN1057). Maximum working pressure 16.0 bar. Maximum operating temperature 85°C.
Range of spherical valves with various operating members, brass bodies, brass balls, FKM ‘O’-rings or EPDM ‘O’-rings (S84W series only) and PTFE seats. Maximum working pressure 40.0 bar. Maximum operating temperature 85°C.
Spherical valve (lever operated) with a DZR brass body, brass ball and PTFE seat. The second outlet incorporates two approved check valve cartridges, verified by test (suitable for backflow protection against Fluid Category 3). There is a test port located between the check valve cartridges. For use with copper pipe manufactured to BS EN 1057. Maximum working pressure 16.0 Bar
Non-metallic materials and components comply with BS6920 at 65°C
Range of ‘IBall Vortex’ flow through valves with brass body and EPDM ‘O’-rings incorporating a plastic spherical valve and a drain tap. Maximum working pressure: 16.0 bar.
Non-metallic materials and components comply with BS6920 at 85°C
Range of spherical valves with nickel plated brass bodies, chromium plated brass balls, PTFE seals, NBR and/or FKM ‘O’-rings. incorporates a stainless-steel strainer. Also incorporate a magnet. Maximum working pressure: See PN in brackets under model. Maximum operating temperature: Cold water use only.
Range of spherical valves with brass bodies and chrome plated brass ball, PTFE washer and EPDM `O` ring and various operating methods. Maximum working pressure 10.0 or 40 bar (see model).
Non-metallic materials and components comply with BS6920 at 85°C
Range of gate valves with a non-rising spindle with a handwheel operating member or lockshield connection. All models have brass or DZR brass body and brass wedge. For use with copper pipe (manufactured to EN1057). Maximum working pressure 16.0 bar.
Non-metallic materials and components comply with BS6920 at 85°C
Range of screw down valves with brass bodies, , EPDM washers and PTFE seats. Compression connection to be used with copper pipe manufactured to EN1057. Maximum working pressure 16 bar. Maximum operating temperature 85°C.
Electrolytic scale inhibitor with nickel plated copper bodies, for use with copper pipe manufactured to BS EN 1057. Maximum working pressure 12.0 bar. Cold water use only.
Electrolytic scale inhibitors with nickel plated copper bodies, for use with copper pipe manufactured to BS EN 1057. Maximum working pressure 12.0 bar. Cold water use only.
Range of magnetic, electrolytic or combined magnetic & electrolytic scale inhibitors with nickel plated copper bodies, for use with copper pipe manufactured to BS EN 1057. Maximum working pressure 12.0 bar. Cold water use only.
Range of magnetic, electrolytic or combined magnetic & electrolytic scale inhibitors with nickel plated copper bodies, for use with copper pipe manufactured to BS EN 1057. Maximum working pressure 12.0 bar. Cold water use only.
'RC851 S'. Factory applied, mustard coloured (once mixed), two-component epoxy coating. Mix parts A & B in a 3:1 volume ratio and apply as per manufacturer's TDS reference 'NT-0230-UK-081222-A', dated 08/12/22. Cure for 15 hours@70°C. For use with water up to 70°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'EBYK' Georgios Peftitselis S.A. Enamel Coating'. Factory applied, blue coloured enamel coating. Apply as per manufacturer's data sheet 'MS1555A' dated 12-10-18. Cure for 14 minutes@840°C. For use with water up to 85°C. This material is only approved for the curing conditions that appear on the approval. If the curing conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'SGPAM-CN-WB01 - Black'. Factory applied, black coloured water based coating. Apply as per manufacturer's Technical Data Sheet 'PAMPIPE-TDC-WA04'. Cure for 30 min at 50°C plus 7 days at 23°C. For use with water up to 23°C. This material is only approved for the curing conditions that appear on the approval. If the curing conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'CEC-GFS Enamel, Black Blue RAL5004'. Factory applied, blue/black (appears black) coloured, enamel coating. Apply as per manufacturer's instructions 'ZZ-Ins001', dated '2021.01.01'. GFS-G base glaze: dry for 15 Minutes at 200°C then fire for 12 minutes at 870ºC. GFS-S surface glaze: dry for 15 Minutes at 200°C then fire for 10 minutes at 830ºC. For use with water up to 85°C. This material is only approved for the drying and firing conditions that appear on the approval. If the drying and/or firing are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Hempadur 35560 Light grey (10500), Light red (50900) & Cream (20320)'. Factory applied, grey, light red coloured & Cream, two-component epoxy coatings. Each colour can be used as a base or topcoat and as a two-coat system. Mix base and curing agent in a 6.8:2 volume ratio. Apply Light Grey and Light Red as per manufacturer's Application Instructions issued 'November 2019'. Apply Cream as per manufacturer's Product Data Sheet dated 'December 2023'. Cure Coat 1 for 16 hours@20°C. Cure Coat 2 for 7 days@20°C. Between December 2022 and November 2024, the Light Grey and Light Red were for use with water up to 40°C. Between December 2024 and December 2027, Light Grey and Light Red are for use with water up to 60°C. The Cream coating was added to the approval in May 2025 and is for use with water up to 60°C. These materials are only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the materials are not covered by the scope of the approval.
'Welmortar-III'. Factory applied, grey coloured cement mortar. Mix cement, sand and water in a mass ratio of 2:3:0.85. Apply as per manufacturer's Standard Operating Procedure 'WDIPL/QA/WI/14A', revision '0', dated '01.10.2021'. Cure for 21 days at 30°C & 70% humidity. For use with water up to 65°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
‘Tankguard DW White’ & ‘Tankguard DW Grey’. Site applied, two-part epoxy coatings. ‘Tankguard DW White’ may be used as a one-coat or two-coat system. ‘Tankguard DW Grey’ may be used as a one-coat or two-coat system. ‘Tankguard DW White’ & ‘Tankguard DW Grey’ may be used as a two-coat system, with either White or Grey as the water-contact coat. ‘Tankguard DW White’ & ‘Tankguard DW Grey’ each comprise of two parts (A & B) which are to be mixed in a volume ratio of 2:1 before applying as per manufacturer's Application Guide issued '17 October 2022'. Cure each coat for 7 days@23°C. For use with water up to 23°C. These materials are only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval, then the materials are not covered by the scope of the approval.
'Tiefill'. Site applied, grey coloured cementitious repair mortar. Mix Tiefill with water in a weight ratio of 9.4:1 and apply in accordance with manufacturer’s instructions for use 'bulletin no. TFILL/031/003, issued 'July 2020'. Cure for 21 days@7°C. For use with water up to 23°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'GPS Black PE100 Type V Pipe'. Black coloured, extruded PE100 pipe. For use with water 23°C.
'Topline PE100 HDPE Electrofusion/Butt Fusion Fitting'. Black coloured, injection moulded, PE100 (HDPE) fitting. For use with water up to 23°C.
'S-Ion PE100 Fittings'. Blue coloured, injection moulded PE100 fittings. For use with water up to 65°C.
'GPS Excel Black PE100 Pipe'. Black coloured, extruded PE100 pipe. For use with water up to 23°C.
'Borsafe ME3440 (black), Borsafe ME3444 (blue) & Borsafe ME3440-W (black)'. PE80 materials suitable for injection moulding and extrusion purposes. For use with water up to 60°C.
'PPE HY3140G'. Black coloured, injection moulded PPE material. For use with water up to 85°C.
'DIC.PPS CZL-5000'. 'DIC.PPS CZL-5000-U' was added to the approval in September 2023. Black coloured, injection moulded PPS materials. For use with water up to 85°C.
'COD.2011'. Black coloured, injection moulded polypropylene compression fitting. For use with water up to 23°C.
'RP2400'. White coloured, extruded polypropylene pipe. For use with water up to 85°C.
'BOSS 79024607'. White coloured, extruded PTFE tape. For use with water up to 85°C.
'DF201'. White coloured, extruded PTFE tape. For use with water up to 85°C.
'COD.2028' valve body. Black coloured, injection moulded PVC valve body. For use with water up to 23°C.
‘EP70A9OF’. Black coloured, compression moulded EPDM rubber material. Shore hardness 70. Tested in-radius size 1.06mm For use with water up to 23°C.
'AA6KWZ, AA7KWZ, AA8KWZ and AA9KWZ'. Black coloured, compression moulded EPDM materials with a shore hardness of between 60 & 88. Tested in-radius size 1.0mm. AA6KWZ is for use with water up to 65°C. AA7KWZ, AA8KWZ and AA9KWZ are for use with water up to 23°C.
'HW-EPDM'. Black coloured, compression moulded EPDM sheet materials. Shore hardness 50, 60, 70 and 80. Tested in-radius size 1.0mm. The 50 shore hardness material is for use with water up to 65°C. The 60, 70 & 80 shore hardness materials are for use with water up to 60°C.
SIL4010, SIL5010 & SIL6010 white translucent. SIL4010, SIL5010, SIL6010 & SIL7010 blue. SIL4010, SIL5010, SIL6010 & SIL7010 red. SIL4010, SIL5010, SIL6010 & SIL7010 yellow. Compression moulded silicone rubber materials. Shore hardness between 40 & 70. Tested in-radius size 1.0mm. For use with water up to 85°C.
'Berner Green Paste'. Green coloured, polymer sealing paste. Apply as per manufacturer's Technical Data Sheet '46845(P)', dated 'December 2019'. For use with water up to 85°C.
'KITAN X FV60 HWR'. Black coloured, injection moulded, Polyarylamide material. For use with water up to 85°C.
'KITAN X FV50 HWR'. Black coloured, injection moulded, Polyarylamide material. For use with water up to 85°C.
Range of deck mounted taps for cold or premixed water with stainless steel bodies. Flow is controlled by a solenoid valve activated via an infra-red sensor, and the spout outlet incorporates a plastic aerator. Supplied with a stainless steel braided PEX lined flexible connection hose. Maximum working pressure 8.0 bar.
Non-metallic materials and components comply with BS6920 at 65°C
Range of wall mounted, single hole, single outlet (fixed) tap assemblies (chromium plated brass) with a solenoid valve controlling the flow and activated via an infra-red sensor. The spout outlet incorporates a plastic aerator. Supplied with a stainless steel braided PEX lined flexible connecting hose. Maximum working pressure 8.0 bar.
Non-metallic materials and components comply with BS6920 at 65°C
Range of single hole, single outlet (fixed) electronically controlled tap assemblies (chrome plated brass). Flow is controlled by a solenoid valve activated by via an infra-red sensor and the temperature is controlled via a ceramic disc headwork with a dome type operating member. The spout outlet incorporates a plastic aerator. The product is supplied with a single check valve assembly (verified by test suitable for backflow protection against Fluid Category 2) and the inlet incorporates a stainless-steel strainer. Maximum working pressure 10 Bar
Non-metallic materials and components comply with BS6920 at 60°C
Range of single hole, single outlet (fixed) electronically controlled tap assemblies (chromium plated brass). Flow is controlled by a solenoid valve activated via an infra-red sensor. The spout outlet incorporates a plastic aerator. The main body incorporates a stainless-steel strainer prior to the solenoid. Maximum working pressure 8.0 Bar.
Non-metallic materials and components comply with BS6920 at 65°C
Range of deck mounted taps for cold or premixed water (chromium plated brass). Flow is controlled by a solenoid valve activated via an infra-red sensor. The inlet hoses have stainless steel strainers and incorporate approved check valve cartridges, however, the complete products have not been fully tested to demonstrate they provide backflow protection. The spout outlet incorporates a plastic aerator. Maximum working pressure 8.0 bar.
Non-metallic materials and components comply with BS6920 at 65°C
Range of wall mounted tap assemblies for cold or premixed water with chromium plated brass bodies. Flow is controlled by a solenoid valve activated via an infra-red sensor and the spout outlets have plastic aerators. Supplied with stainless steel braided PEX lined connection hoses. Maximum working pressure 8.0 bar.
Non-metallic materials and components comply with BS6920 at 65°C
Range of single hole, single outlet, electronically controlled tap assemblies (chrome plated brass body). The flow is controlled by a solenoid valve activated via an infra-red sensor. The spout outlet incorporates a plastic aerator. Supplied with a stainless steel braided PEX lined flexible connection hose and a manual lever for controlling the temperature. Maximum working pressure 8.0 bar.
Non-metallic materials and components comply with BS6920 at 65°C
Range of deck mounted single hole, single outlet (fixed) electronically controlled tap assemblies (stainless steel for models 236303 & 236404 only or chromium plated brass for all others). Flow is controlled by a solenoid valve activated by via an infra-red sensor. The spout outlet incorporates a plastic aerator. The inlets incorporate stainless steel strainers and the products are supplied with stainless steel braided PEX line connection hoses. Maximum working pressure 8.0 Bar.
Non-metallic materials and components comply with BS6920 at 65°C
Range of single hole, single outlet, electronically controlled tap assemblies (chrome plated brass body). The flow is controlled by a solenoid valve activated via an infra-red sensor. The spout outlet incorporates a plastic aerator. Supplied with a stainless steel braided PEX lined flexible connection hose. Maximum working pressure 8.0 Bar.
Non-metallic materials and components comply with BS6920 at 70°C
Range of side and bottom entry BS1212-4 fill valves with plastic bodies. Maximum working pressure 10.0 bar. Coldwater use only.
Range of bottom entry BS1212-4 telescopic fill valves with plastic bodies. Maximum working pressure 10.0 bar. Cold water use only.
Page 89 of 233
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.