‘Aquapoint APIII’ range of direct unvented under basin or over basin (wall mounted) electrically heated, enamel lined insulated steel storage cylinders. The cylinders are supplied with an expansion relief valve set at 6.0 bar. Maximum working pressure 5.5 bar. Maximum operating temperature 75°C.
Varipoint range of unvented water heaters with copper bodies, fitted with a temperature & pressure relief valve (7.0 bar) and supplied with a pressure relief valve (6.0 bar). Maximum working pressure 5.5 bar. Maximum operating temperature 85°C.
Range of wall hung, gas fired, combination boilers providing domestic hot water via a plate heat exchanger. The primary circuit incorporates an integral expansion vessel and a pressure relief valve set at 3.0 bar. The product is supplied with a rigid pipe filling loop, followed by a separate isolation valve. The filling loop pipe attaches to the cold water inlet valve which incorporates a double check valve assembly (verified by test, suitable for backflow protection against Fluid Category 3) on the branch to the filling loop. The primary circuit includes an isolation valve on the flow and return and is also supplied with two loose 22mm compression isolation valves and a filter. Maximum working pressure of the primary circuit is 2.5 bar and the maximum supply pressure to the secondary circuit is 10.0 bar. Max operating temperature 65°C.
Permanent filling/ pressurisation device for primary heating and chilled water closed circuits in domestic and non-domestic premises. The mains and closed circuit system pressures are continuously checked by two pressure sensors and their differential monitored by microprocessors. In the event of a fall in system pressure, and only if the mains pressure is adequate, a solenoid valve operates to allow water into the system. At all other times a second solenoid valve drains the fill chamber to waste, via tundish (meeting the requirements of an air gap to drain), and allowing air to be admitted via an automatic air vent to create an atmospheric disconnection across the transfer chamber. Maximum working pressure 6.0 Bar. Cold water use only.
Range of vertical multistage booster pumps, with stainless steel bodies and impellors. Maximum working pressure: See models Maximum working temperature 85°C.
Range of shower handsets with a black plastic body and EPDM ‘O’-rings. Model includes a trigger mechanism that alters the spray pattern. Maximum operating temperature 60°C.
Range of shower handsets with chrome plated ABS bodies incorporating NBR o rings. Maximum operating temperature 60°C.
Range of shower handsets (chrome plated brass), shower hoses, handset brackets and cover plates. The shower handset inlets incorporate stainless-steel strainers and approved check valve cartridges, however, the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum operating temperature 60.0°C
Range of shower handsets with plastic bodies (chrome plated or white finish). Maximum operating temperature 60.0°C
Range of shower handsets and shower heads. The shower handsets have a plastic body (white), NBR ‘O’-rings, and a coloured locking ring around the shower face (see model section). The shower heads have a plastic body (white or chrome plated 02-093173 model), NBR ‘O’-rings, directional adjustment (ball joint) and a coloured interlocking ring either surrounding or central to the shower face (except for the 02-093165 and 02-093173 models which have no ring). The Wall shower T-L models have a combined NBR washer and stainless steel strainer on the inlet.
Wall mounted shower head arm incorporating a chrome plated brass body and EPDM O-rings. Maximum operating temperature 85°C.
Overhead shower outlet with a chromium plated brass body. The inlet incorporates a plastic flow restrictor. Maximum operating temperature 60°C.
Pillar tap incorporating (chromium plated) brass body quarter turn ceramic disc headwork with a single lever operating member. The spout outlet incorporates a plastic flow straightener. Maximum working pressure 6.0 bar. Maximum operating temperature 85°C. The product is supplied with metal backnuts.
Range of pillar taps (chromium plated brass), incorporating quarter turn ceramic disc headworks with single lever, dome type or cross top operating members and plastic backnuts. The spout outlets incorporate a plastic flow straightener. Maximum working pressure 10.0 bar. Maximum operating temperature 60°C.
Range of pillar taps (chromium plated brass), incorporating quarter turn ceramic disc headworks with single lever, dome type or cross top operating members and plastic backnuts. The spout outlets incorporate a plastic flow straightener. Maximum working pressure 10.0 bar. Maximum operating temperature 60°C.
Range of wholesome-water nickel plated brass manifolds for use with ‘Emmeti Gerpex RA’ Pexb/Al/Pexb Multilayer pipe and ‘Emmeti Alpert’ PERT/AL/PERT Multilayer Pipe. Maximum working pressure 10.0 bar. Maximum operating temperature 95°C. Range of closed circuit use nickel plated brass manifolds for use with ‘JG Speedfit Layflat Polybutylene Barrier Pipe (models 10BPB & 15BPB)’. Maximum working pressure 3.0 bar. Maximum operating temperature 92°C.
Wall mounted, exposed, manual blending valve (brass body, various finishes - see model), incorporating a ceramic cartridge headwork with a single lever operating member. The shower outlet incorporates an approved check valve cartridge, however, the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum working pressure 10.0 bar. Maximum operating temperature 60°C.
Range of wall mounted, thermostatic blending valves (chrome plated brass bodies) incorporating quarter turn ceramic disc headwork with a single lever operating member. Temperature is independently controlled via a thermostatic cartridge with cross top operating members. Both inlets incorporate approved single check valve cartridges, however, the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum working pressure 5.0 bar. Maximum operating temperature 60°C.
Range of wall mounted, thermostatic blending valves (chrome plated brass bodies) incorporating quarter turn ceramic disc headwork with a single lever operating member. Temperature is independently controlled via a thermostatic cartridge with cross top operating members. Both inlets incorporate approved single check valve cartridges, however, the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum working pressure 5.0 bar. Maximum operating temperature 60°C.
Range of wall mounted, bar type thermostatic blending valves (chromium plated brass) incorporating a quarter turn ceramic disc headwork controlling the flow with dome operating member incorporating a manual override button. The temperature is controlled by a thermostatic cartridge with dome or cube type operating member incorporating a manual override button. Both inlets incorporate a stainless-steel strainer and single check valve cartridge (however, the complete product has not been fully tested to demonstrate it provides backflow protection). Maximum working pressure 10.0 bar. Maximum operating temperature 65°C.
Wall mounted thermostatic shower valve (chromium plated brass bodies), incorporating a quarter turn ceramic disc headwork diverting the flow between overhead shower and handset with cube type operating member. Temperature is controlled independently via a thermostatic cartridge with a cube type operating member that incorporates a manual override button. The product incorporates a fixed riser and overhead shower and is supplied with a shower hose and handset. Both inlets incorporate stainless steel strainers and approved check valve cartridges, however, the complete products have not been fully tested to demonstrate that they provide backflow protection. Maximum working pressure: 5.0 Bar Maximum operating temperature: 60°C.
Electronically controlled thermostatic shower mixing valve with a plastic body. Temperature is controlled via two motorised valves and a thermistor. The product also incorporates a pump and plastic filters on each inlet. Maximum working pressure 7.0 bar. Maximum working temperature 65°C.
Range of wall mounted, concealed, thermostatic shower valves with cast brass bodies, incorporating a ceramic cartridge headwork controlling the flow with a single lever operating member. The temperature is controlled independently via a thermostatic cartridge with a single lever operating member. Maximum working pressure 10.0 bar. Maximum operating temperature 60°C.
Range of butterfly valves incorporating blue epoxy coated ductile iron bodies and discs. Maximum working pressure 16.0 bar. Maximum operating temperature 85°C.
Range of wall mounted concealed diverter valves with a plastic body. The flow is controlled to two outlets via solenoid valves. Maximum working pressure 5.0 Bar. Maximum working temperature 65°C
Range of high and low pressure diaphragm float operated valves with brass body and backnuts. Maximum working pressure 8.0 or 10.0 bar (please refer to model). Cold water use only.
Range of piston type float operated inlet valves with brass bodies and backnuts. Maximum working pressure 8.0 or 10.0 bar (please refer to model). Cold water use only.
Manually operated thermally actuated regulating valves with bronze bodies and EPDM O-rings. Flow is controlled by a rising spindle headwork. Maximum working pressure 16.0 bar. Maximum operating temperature 90°C.
Range of pilot operated, adjustable, pressure reducing control valves, incorporating stainless steel bodies & strainers and EPDM ‘O’ rings & diaphragm. Auxiliary components include stainless steel tubing and isolation valves. The product is available with the following adjustable outlet pressures: 0 - 3.0 bar (silver spring), 1.0 - 8.0 bar (black spring), 1.0 - 16.0 bar (red spring). Maximum supply pressure 16.0 bar. Maximum operating temperature 65°C.
Range of spherical valves with brass (CW617N) or DZR brass (CW511L) bodies (chrome plated, nickel plated or without plating - see model), chrome plated brass ball and a range of different operating members (see model). Compression connections are for use with copper pipe (manufactured to EN 1057). Maximum working pressure 10.0 bar. Maximum operating temperature 85°C.
Range of ball valves with nickel plated brass bodies, chrome plated brass ball, PTFE seats, and either lever or T handle operating members (see models). Maximum working pressure 16.0 to 64.0 Bar (Size & model dependant, see models) Maximum working temp 85°C
Range of spherical valves (inline, angled and tee) with chrome plated brass bodies and ball. Maximum working pressure 10.0 Bar Maximum operating temperature 60.0°C
Range of spherical valves with nickel plated brass bodies, chromium plated brass balls, PTFE seals, NBR and/or FKM ‘O’-rings. 140, 140M, 141 & 141M series models incorporate a stainless-steel strainer. 140 & 141 series models also incorporate a magnet. The 121 & 122 series models are 3-way valves. Maximum working pressure: See PN in brackets under model. Maximum operating temperature: Cold water use only.
Manifold spherical valve with DZR brass body and ball (chrome plated), incorporating a single lever type operating members and a single check valve assembly (verified by test as suitable for backflow protection against Fluid Category 2). For use with with copper pipe manufactured to EN1057. Maximum working pressure 16.0 bar. Maximum operating temperature 85°C.
Range of gate valves with brass bodies and wedge with either a lock shield or non-rising spindle operating mechanism for use with copper pipe (manufactured to EN 1057). Maximum working pressure 6.0 Bar Maximum operating temperature 95.
Range of resilient seated gate valves with blue epoxy coated ductile iron bodies, and an EPDM wedge, gasket and ‘O’-ring. with a a non-rising spindle, both have a handwheel operating member. Maximum working pressure 25.0 bar. Maximum operating temperature 85°C.
Range of gate valves with a non-rising spindle and a handwheel operating member with a brass body and brass wedge. For use with copper pipe (manufactured to EN1057). Maximum working pressure 16.0 bar. Maximum operating temperature 85°C.
Range of ion exchange water softeners (salt regenerated) for domestic use. Maximum working pressure 8.3 bar. Cold water use only.
'Endolac 245.30 FGC'. Factory applied, black coloured, bituminous coating. Apply as per manufacturer's technical data sheet dated 04/05/2022. Cure for 7 days@20°C. For use with water up to 60°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'AO-96 Sealing Ring'. Black coloured, compression moulded, ceramic sealing ring. For use with water up to 85°C.
'Eurokote 468 Thixo Brun Rouge'. Factory applied, red/brown coloured, two-part epoxy coating consisting of a resin and hardener. Mix resin and hardener in a weight ratio of 77:23 and apply as per manufacturer's Data Sheet dated '10/05/2019'. Cure for 10 days@20°C. For use with water up to 60°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'PPA 571 ES Blue 536'. Factory applied, blue coloured polyolefin coating. Apply as per manufacturer's instructions dated '08/2022'. Cure for 20 minutes@200°C. For use with water up to 23°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Eurokote 468 Thixo Brun Rouge 500'. Factory applied, red/brown coloured, two-part epoxy coating consisting of a resin and hardener. Mix resin and hardener in a weight ratio of 70:30 and apply as per manufacturer's Technical Data Sheet version edit '23/01/202. Cure for 10 days@20°C. For use with water up to 60°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'NOA FWT BUFF/NOA FWT WHITE (ORGA1000 NOA BUFF/ORGA 1000 NOA WHITE). NOA FWT BUFF/NOA FWT BULE (ORGA1000 NOA BUFF/ORGA 1000 NOA BULE). NOA FWT BUFF/NOA FWT CREAM (ORGA1000 NOA BUFF/ORGA 1000 NOA CREAM)'. Factory applied, two-component white, blue & cream coloured epoxy coatings. Mix base and hardener in a 3.71:1 volume ratio and apply as per manual reference '14-11' dated 'July 2019 (ES)'. Cure for 16 hours@23°C. For use with water up to 23°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the materials are not covered by the scope of the approval.
'UPS 505 WAU Blue & Grey'. Site applied, two-component polyurethane coatings which are available in blue or grey colours (once mixed). Mix Part A (blue or grey opaque liquid) with Part B (amber, translucent liquid) in a 100:30.5 weight ratio and apply as per manufacturer's technical data sheet ‘TDS – UPS505WAU - Version 6 – August 2022'. Cure for 14 days@7°C. For use with water up to 23°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the materials are not covered by the scope of the approval.
'Belzona 5892'. Site applied, epoxy coating consisting of Belzona 5892 (white – Parts A & B) & Belzona 5892 (grey – Parts A & B). Belzona 5892 (white – Parts A & B) are mixed in a weight ratio of 5.7:1 and then applied as a first coat (no cure) in accordance with manufacturer’s instructions for use ‘FN10106’, publication number ’04-11-20(01)’. Belzona 5892 (grey – Parts A & B) are mixed in a weight ratio of 5.7:1 and then applied to the white in accordance with manufacturer’s instructions for use ‘FN10106’, publication number ’04-11-20(01)’. The final coating is then cured for 24 hours@30°C. For use with water up to 85°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the materials are not covered by the scope of the approval.
'Polyurea Rayston'. Site applied, blue coloured, two-component polyurea coating consisting of Component A, Component B and Component C (Pigment Paste). Mix & apply as per manufacturers datasheet dated 13/09/22. For use with water up to 60°C. This approval is valid only for the material when it is applied by experienced, suitably trained applicators that are authorized and/or certified by Krypton Chemical, S.L. The authorization, training and certification of the local applicators are the responsibility of Krypton Chemical, S.L. and not the responsibility of WRAS.
'Interline 925 Cream'. Site applied, cream coloured, two-component, solvent free epoxy coating. Mix part A (white liquid) with part B (yellow liquid) in a volume ratio of 3:1 and apply as per manufacturer’s TDS ref. ‘2252’ dated 17/12/2020. Cure for 7 days@25°C. For use with water up to 60°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Devi Flosto GRP (SMC) Hot Press Moulded Tank Panels' (manufactured from SMC 523/35). Grey coloured, hot press moulded GRP panels with a thickness of between 3.0mm & 16.0mm. For use with water up to 23°C.
'Silicopaste 312500'. White coloured silicone grease. Apply as per manufacturer’s instructions. For use with water up to 65°C.
Page 41 of 177
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.