Range of in-line, adjustable, pressure reducing valves with DZR brass bodies and incorporating a stainless steel strainer. Maximum supply pressure 16.0 bar. Outlet pressure range 1.0 to 6.0 bar with an inlet pressure of up to 10 bar Outlet pressure range 2.0 to 6.0 bar with an inlet pressure above 10 bar Maximum operating temperature 60°C.
Range of bronze swing gate valves incorporating a bronze disc with a metal-to-metal seal. Maximum working pressure 20.0 bar. Maximum operating temperature 85°C.
Range of spherical valves with stainless steel bodies, PTFE seats and silicone O-rings. Maximum working pressure 10.0 bar. Maximum operating temperature 90°C.
Range of spherical valves with a brass body, brass ball, PTFE seats and lever type operating members. Maximum working pressure 40.0 Bar Maximum operating temperature 65.0°C
Range of angle valves (brass bodies – various finishes), incorporating non-rising spindle headworks with a dome type operating members and NBR O-rings and PTFE Seals. Maximum working pressure 10 bar. Maximum operating temperature – Cold Water Use
Electronically controlled spherical valve with smart water leakage shut off, incorporating ceramic pressure sensor, stainless steel ball and EPDM O-rings. Maximum working pressure 10 bar. Maximum operating temperature 85°C
Range of lever operated spherical valves with (nickel plated) brass bodies, incorporating chromium plated brass balls and PTFE seats. Max working pressure 32 bar. Max operating temperature 100℃.
Range of spherical valves with nickel plated brass bodies, chromium plated brass balls and various operating members (see models). Products incorporate EPDM O-rings and PTFE seats. Maximum working pressure ½” – 1” 30 bar, 1 ¼” – 2” 25 bar. Maximum operating temperature 100°C.
Range of ball valves with DZR brass bodies and either a chrome plated DZR brass ball (¼-1" sizes) or stainless-steel ball (1¼-2" sizes). The valves are available with lock shield, butterfly or single lever operating members. The threaded end connections have octagonal spanner flats. Maximum working pressure 25.0 bar. Maximum operating temperature 85°C.
Range of lever operated spherical valves with brass bodies (chromium plated), incorporating chromium plated balls and PTFE seats. Maximum working pressure 16.0 bar. Maximum operating temperature 85°C.
Range of spherical valves with nickel plated brass bodies, incorporating PTFE seats and chromium plated brass balls. Valves are operated by butterfly type handles. Maximum working pressure 25.0 bar. Maximum operating temperature 85°C.
Range of spherical valves with stainless steel bodies, chrome plated brass ball and PTFE seats. Maximum working pressure 68.9Bar.
Non-metallic materials and components comply with BS6920 at 85°C
Range of hand wheel operated gate valves with blue epoxy coated ductile iron bodies and EPDM wedge. Maximum working pressure 16.0 Bar. Maximum operating temperature 65.0°C.
Range of resilient seated gate valves incorporating blue epoxy coated ductile iron body and EPDM gaskets with a handwheel operating member. Maximum working pressure 16.0 Bar Maximum operating temperature 23.0°C
Range of gate valves incorporating blue epoxy coted ductile iron bodies, ductile iron wedges encapsulated in EPDM and an EPDM gasket and seal. The valves are operated via a non-rising spindle with a hand wheel operating member. Maximum working pressure 16.0 bar. Maximum operating temperature 85°C.
Range of screw down stop valves with brass bodies, NBR seals and ‘T’ type operating members. Compression connection to be used with copper pipe EN1057 only. Maximum working pressure 16 bar. Maximum operating temperature 85°C.
Range of manually operated balancing valves with bronze bodies, DZR brass disc and EPDM rubber 'O’-rings. Both models have test points. The F9506 models also have a drain point on the high-pressure test side. Maximum working pressure 25.0 bar. Maximum operating temperature 100°C.
Range of bedpan washing & disinfection machines. The flow is controlled by a solenoid valve and discharged via a type `AB` airgap (verified by test - suitable for backflow protection against fluid category 5). Maximum working pressure - See models Maximum operating temperature - 90 °C
Range of commercial washing machines with flow controlled by solenoid valves and discharged via type AB air gap assembly (verified by test - suitable for backflow protection against fluid category 5). The inlets incorporate approved check valve cartridges, however, the complete product has not been fully tested to demonstrate it provides backflow protection Maximum working pressure 5 Bar. Maximum operating temperature 60°C.
Range of in-line electrolytic scale inhibitors with copper bodies, for use with copper pipe manufactured to BS EN 1057 Maximum working pressure 20.0 bar. Cold water use only
Range of inline water conditioners with stainless steel bodies and catalytic alloy core. Maximum working pressure 16.0 bar. Maximum operating temperature 100°C.
‘G5 C’ command centre providing chilled (filtered) water via an electronically controlled tap (not supplied). Flow is controlled via a combination of solenoid valves and electronic pumps to the outlets. The products are supplied with a filter cartridge. The inlet to the command centre incorporates two approved check valve cartridges, however, the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum inlet supply pressure 5.0 bar. Cold water use only.
‘G5 CS’ command centre providing chilled or chilled sparkling water (both filtered) via an electronically controlled tap (not supplied). Flow is controlled via a combination of solenoid valves and electronic pumps to the outlets. The product incorporates a pressure reducing valve (adjustable outlet pressure between 2.25 and 2.75 bar) on the supply to the carbonator unit. The carbonator inlet incorporates a non-return valve. The product is supplied with a filter cartridge. The inlet to the command centre incorporates two approved check valve cartridges, however, the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum inlet supply pressure 5.0 bar. Cold water use only.
'ELECTROCOAT BP 1119'. Factory applied, black coloured Bituminous Paint. Apply as per manufacturer's TDS Document No: 'ECL/ TDS / BP-1119-Bituminous Paint', Issue Date '10-Aug-20', Version No: '01'. Cure for 12 minutes at 45°C, followed by 10 hours at 28°C. For use with water up to 65°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
‘PRIMER NATZINC EP9015 SC PART A’ Primer for use with ' HYDRALFUN AC BLEU PAM RAL5005-CZL8190 ' top-coat. Factory applied, blue coloured (once applied) primer and finish-coat. Mix base:hardener of primer in a 100:10 weight ratio and apply as per manufacturer’s TDS February 2024. Then apply top-coat as per manufacturer’s TDS February 2024. Cure for 21 days@23°C. For use with water up to 50°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Hempathane PW 35660 blue & off-white`. Factory applied, two-component polyurethane liquid coating consisting of a base and curing agent. Mix base and curing agent in a 3:1 volume ratio and apply as per product data sheet dated December 2023. Cure for 7 days@20°C. For use with water up to 35°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Hempadur 35560 Cream'. Factory applied, two-component, cream coloured epoxy coating which can be applied as a one-coat or a two-coat system. Mix base and curing agent in a 6.8:2 volume ratio and apply as per manufacturer's Product Data Sheet dated 'December 2023'. Cure each coat for 7 days@20°C. For use with water up to 60°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
‘Sikagard®-180’. Site applied, grey coloured, two-component epoxy coating consisting of Part A (grey coloured liquid) and Part B (colourless liquid). Mix Part A and Part B in a mass ratio of 87:13 and apply as per manufacturer's TDS 'MBS_CC-UAE/Pr_180_05_18/v9/02_22/v10/05_23/v11/01_24'. Cure coat 1 for 36 hours@20°C. Cure coat 2 for 21 days@20°C. For use with water up to 40°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'LOCTITE® SF 770™' (known as 'LOCTITE 770'). Site applied, clear cyanoacrylate primer. Apply as per manufacturer's technical data sheet dated May 2021. Cure for 30 seconds@20°C. For use with water up to 85°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
‘Sikagard®-1814 - RAL 7035’. Site applied, grey coloured (once mixed), two-component epoxy polysulfide resin coating. Mix Part A (light grey, opaque liquid) and Part B (light yellow, translucent liquid) in a 78:22 weight ratio and apply 2 coats as per manufacturer’s TDS ‘MBS_CC-UAE/Pr_1814_06_23/v1/01_24’. Cure coat 1 for 9 hours@25°C. Cure coat 2 for 14 days@25°C. For use with water up to 50°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Klinger K10'. White coloured, braided compression packing. For use with water up to 85°C. For use only as a gland packing material having been tested at a reduced surface area to volume ratio.
'Graphalloy Bushing Grade GM 690'. Grey coloured, resin impregnated, carbon/graphite material. For use with water up to 23°C.
'Ecoflex HT'. White coloured (translucent), extruded TPS hose. Shore hardness 88. Tested in-radius size 0.62mm. For use with water up to 85°C.
'Polimid A30GF Natural WR'. Natural (light grey coloured), injection moulded PA66 material. For use with water up to 85°C.
'Icorene 1440 NAT & Icorene 1440 BLK 9001'. Natural (appears off-white) & black, rotationally moulded polyethylene materials. For use with water up to 23°C.
'GF PVC-U Metric Pipe'. Dark grey coloured, extruded u-PVC pipe. For use with water up to 60°C.
'MILGERLAN EBONITE 1065G'. Black coloured, calendered natural rubber material. Shore hardness 65. Tested in-radius size 3.1mm. For use with water up to 23°C.
'ERIKS 559706'. Black coloured, EPDM 'O' ring with a vulcanised joint, manufactured by extrusion. Shore hardness 70 ShA. Tested in-radius size 8.0mm. For use with water up to 23°C.
'EP70-S3150/B1-73898 'O' rings'. Black coloured, injection moulded EPDM 'O' rings. Shore hardness 70. Tested in-radius size between 0.5mm & 3.0mm. For use with water up to 85°C.
'3E60B11P/3E60B18P & 3E70B03P/3E70B16P'. Black coloured, compression moulded EPDM materials. Shore hardness 60 & 70. Tested in-radius size 1.0mm. For use with water up to 85°C.
Range of single-hole, single outlet (fixed) electronically controlled combination tap assemblies (brass bodies – chrome plated). The flow is controlled by a solenoid valve activated via an infra-red sensor. The temperature is controlled independently via a single lever operating on the side of the body. The spout outlets incorporate plastic flow straighteners. The inlet hoses incorporate an approved single check valve cartridge, however, the complete assembly has not been tested to demonstrate it provides backflow protection. The products are supplied with single lever spherical valves. Maximum working pressure 5.0 Bar Maximum operating temperature 60.0°C
Wall mounted, single hole, single outlet (fixed) electronically controlled tap assemblies, (chromium plated brass body). Flow is controlled by a solenoid valve activated via an infra-red sensor. The spout outlet incorporates a plastic aerator. The inlet adapters incorporate stainless steel filters and single check valve cartridges verified by test (suitable for backflow protection against Fluid Category 2 ). Maximum working pressure 10.0 bar. Maximum operating temperature 70°C.
Range of side or bottom entry BS1212-4 (2016) compact type float operated valve for WC flushing cisterns. The inlet incorporates a flow regulator. Maximum working pressure 10.0 bar. Cold water use only.
Three-hole, single outlet (fixed), combination tap assembly (brass body – various finishes), incorporating a ceramic cartridge headwork with a single lever operating member and a manual diverter to the shower outlet. The product is supplied with a stainless-steel braided EPDM lined flexible connection hose to connect the head work to the spout outlet. Maximum working pressure 5.0 Bar
Non-metallic materials and components comply with BS6920 at 65°C
Range of spring-loaded resilient trim in-line check valve cartridges with acetal bodies. For insertion into specifically dimensioned bores. Maximum working pressure 16.0 bar. Maximum operating temperature 85°C.
Single hole, single outlet (fixed) over the rim swivel nozzle bidet combination tap assembly (brass body - various finishes) with a ceramic cartridge headwork and single lever operating member. The spout outlet incorporates a plastic flow straightener. The product is supplied with a lever operated pop-up waste (not verified by test). Maximum working pressure 5.0 Bar. Maximum operating temperature 60.0°C.
Range of ¼ turn ceramic disc headworks with brass bodies, EPDM ‘O’-rings and either a red or blue silicone gasket. Maximum working pressure 16.0 bar. Maximum operating temperature 85°C.
Thermostatic cartridge with NBR ‘O’-rings for insertion into specifically dimensioned bores. Maximum working pressure 12.0 bar. Maximum operating temperature 85°C.
Single hole, single outlet (fixed) combination tap assembly (chrome plated brass), incorporating a non-rising spindle headworks with dome type operating members. The spout outlet incorporates a plastic flow straightener. Product is supplied with a lever operated pop-up waste (not verified by test) Maximum operating pressure 10.0 bar. Maximum operating temperature 60°C.
Range of single hole, single outlet (fixed) combination tap assemblies (brass bodies - various finishes), incorporating a ceramic cartridge headwork with single lever operating members. The spout outlets of all models except TAP031 incorporate a plastic aerator. TAP031L Maximum working pressure - 5.0 Bar. Maximum operating temperature 85°C. All other models Maximum working pressure - 10.0 Bar. Maximum operating temperature 65.0°C
Page 160 of 222
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.