Range of heat interface units (HIU) with either twin or single stainless steel copper brazed plate heat exchangers (depending on model) providing heating and hot water (twin unit) hot water only, or heating only. The hot water is generated via a plate heat exchanger. The primary (space heating) circuit incorporates an expansion vessel and a pressure relief valve (set at 3.0 bar). The product incorporates a CAb backflow prevention device (suitable for backflow protection against Fluid Category 3) for filling the heating circuit. The inlet and outlet of all circuits incorporate a lever operated spherical valve. Maximum working pressures and operating temperatures: Primary (district heating): 10.0 bar and 85˚C. Domestic hot water (DHW): 10.0 bar and 60˚C. Secondary (space heating): 2.5 bar and 80˚C.
Immersion temperature sensors with DZR bodies and an EPDM ‘O’-ring (STDW14 model only). Maximum working pressure 15.0 bar. Maximum operating temperature 100°C.
Range of pump docking manifolds with plastic bodies and NBR, EPDM and FKM ‘O’-rings. Maximum working pressure 8.0 bar. Cold water use only.
Range of concealed bathroom boxes with extractable shower hoses. The inlet attached to the concealed box incorporates an approved single check valve cartridge, however the complete product has not been fully tested to demonstrate it provides backflow protection. The outlet of the shower hose also includes a stainless steel strainer. Maximum operating temperature 60°C.
Range of submersible pumps incorporating stainless-steel bodies and plastic impellers. Maximum working pressure 23.0 bar or 36.0 bar (please refer to model). Maximum operating temperature 35°C.
VDROO range of stainless steel multistage centrifugal pumps with stainless steel impellers, diffusers and outer sleeves. The pumps incorporate a Silicone Carbide and EPDM mechanical seal. Maximum working pressure 25.0 bar DIN flange. Maximum working pressure 16.0 bar for oval flange. Cold water use only.
Range of vertical multistage booster pumps, with stainless steel bodies and impellors (AISI304 or 316 see model). Maximum working pressure (model dependent): 4.0 bar models: BMVET(I) 32-10-1 to BMVET(I) 32-40. BMVET(I) 42-10-1 to BMVET(I) 42-20. BMVET(I) 65-10-1 to BMVET(I) 65-20-2. BMVET(I) 85-10-1 to BMVET(I) 85-10. 10.0 bar models: BMVET(I) 1-2 to BMVET(I)1-36. BMVET(I) 2-2 to BMVET(I) 2-11. BMVET(I) 3-2 to BMVET(I) 3-29. BMVET(I) 4-2 to BMVET(I) 4-10. BMVET(I) 8-2 to BMVET(I) 8-20. BMVET(I) 12-2 to BMVET(I) 12-18. BMVET(I) 16-2 t BMVET(I) 16-16. BMVET(I) 20-1 to BMVET(I) 20-17. BMVET(I) 32-50-2 to BMVET(I) 32-100. BMVET(I) 42-30-2 to BMVET(I) 42-50. BMVET(I) 65-20-1 to BMVET(I) 65-30. BMVET(I) 85-20-2 to BMVET(I) 85-30-2. 15.0 bar models: BMVET(I) 2-13 to BMVET(I) 2-26. BMVET(I) 3-31 to BMVET(I) 3-36. BMVET(I) 4-12 to BMVET(I) 4-22. BMVET(I) 32-110-2 to BMVET(I) 32-140. BMVET(I) 42-60-2 to BMVET(I) 42-130-2. BMVET(I) 65-40-2 to BMVET(I) 65-80-1. BMVET(I) 85-30-1 to BMVET(I) 85-60. Maximum operating temperature 100°C.
CM(E)(C) range of electronically operated pumps available in stainless steel, (‘EN 1.4301/AISI304’ or ‘EN 1.4401 /AISI316’) and cast iron. (CMEC models were added October 2023). The pumps are supplied with Sic-Sic mechanical shaft seals and FKM or EPDM seals. Cast iron models: Maximum working pressure 10.0 bar. Cold water use only. Stainless steel models: Maximum working pressure 16.0 bar. Maximum operating temperature 60°C for self-priming models, 99°C for all other models.
Range of pumps with either brass or stainless-steel bodies, stainless steel impellor and NBR ‘O’ rings. 20 & 33 brass series have a maximum working pressure of 16.0 bar. 33 stainless-steel series has a maximum working pressure of 20.0 bar. 22, 24 ,26, 38, 31, 32 & 34 series have a maximum working pressure of 20.0 bar. Cold water use only.
Range of wall mounted shower outlets with brass bodies (various finishes). The 24 004 xxx, 24 014 xxx and 35 279 xxx models are supplied with ceiling mounted shower arm. The 24 005 xxx, 24 015 xxx, 35 275 xxx and 35 280 xxx supplied with wall mounted shower arm. The 24 005 xxx, 24 015 xxx, 35 275 xxx & 35 280 xxx models incorporate stainless steel strainers on the inlet. The 24 014 xxx & 24 015 xxx models incorporate plastic flow regulators on the inlet. Maximum operating temperature 60°C.
Range of interlocked EPDM lined shower hoses assemblies with EPDM gaskets. Maximum operating temperature is 85°C. bar.
Range of wall mounted shower outlets in various finishes. Maximum operating temperature 80°C.
Range of wall mounted shower outlets (chromium plated brass). Models ARMW02 and ARMW05 are supplied with metal backnuts. Maximum operating pressure 10.0 bar. Maximum operating temperature 65°C.
Range of shower outlets with chromium plated bodies. Models P60901 and P61400 have check valves fitted at the inlets however, the complete products have not been fully tested to demonstrate they provide backflow prevention. From July 2023, model P61400 can also be supplied without the check valve at the inlet. Maximum operating temperature 70°C.
Range of shower outlets with chromium plated bodies. Models P60901 and P61400 have check valves fitted at the inlets however, the complete products have not been fully tested to demonstrate they provide backflow prevention. Maximum operating temperature 70°C. Open outlet use only.
Range of in-line `Y`-patterned strainers with bronze bodies incorporating stainless steel mesh strainers and PTFE washers. Maximum working pressure 20.0 bar. Maximum operating temperature 85°C.
Range of in-line `Y`-patterned strainers with either brass or DZR brass bodies (see model) incorporating a stainless steel mesh strainer and a PTFE washer. Maximum working pressure 25.0 Bar. Maximum operating temperature 99.0°C
Range of inline strainers incorporating DZR brass bodies and a stainless steel mesh. Maximum working pressure 25.0 bar. Maximum operating temperature 85°C.
Range of flow switches with brass bodies incorporating EPDM ‘O’-rings, acting as a leak detection system that actuates an integral spherical valve to shut off the water supply. The inlet incorporates a stainless steel strainer. The outlet incorporates an approved check valve cartridge, however, the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum working pressure 16.0 bar. Maximum operating temperature 30°C.
Range of flexible hoses assemblies incorporating a braided outer with TPSiV liner and various brass end connections. Incorporating NBR or EPDM washers and ‘O’-rings. Maximum operating temperature 85°C.
Page 3 of 60
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.