Filling loop assembly consisting of an in-line isolation valve, an in-line double check valve assembly which incorporates an isolation valve (suitable for back flow protection against fluid category 3) and a stainless-steel braided EPDM lined hose. The isolation valves are operated via a single lever. Maximum working pressure 10.0 bar. Maximum operating temperature 85°C.
Range of stainless steel (SUS304/316L) crimp fittings incorporating EPDM ‘O’-rings. For use with Mingshi stainless steel pipes (SUS304/316L). Maximum working pressure 16.0 bar.
Non-metallic materials and components comply with BS6920 at 85°C
Range of press copper crimp fittings with EPDM ‘O’-rings for use with copper tube manufactured to EN 1057. The joints are achieved by means of a crimping tool. For above ground use. Maximum working pressure: 16.0 bar. Maximum operating temperature: 85°C
Hyddro Range of stainless steel (SUS304/316L) crimp fittings incorporating EPDM ‘O’-rings. For use with Hyddro stainless steel pipes (SUS304/316L). Maximum working pressure 16.0 bar.
Non-metallic materials and components comply with BS6920 at 85°C
Range of Hyddro press fittings incorporating EPDM ‘O’-rings. For use with Hyddro (S-1-0509/10/11/12/17/13) PEX-AL-PEX pipe. Maximum working pressure 10.0 bar. Maximum operating temperature 95°C
‘BF’ range of Brass compression fittings for use with copper pipe manufactured to EN1057 Maximum working pressure 10.0 bar. Maximum operating temperature 95°C.
Range of compression fittings incorporating polypropylene bodies, plastic pipe liners, plastic grip rings and EPDM seals. For use with PE100 pipe manufactured to BS EN 12201. Maximum working pressure: 16Bar. Maximum operating temperature: 23°C
Range of brass press fittings for use with copper pipe (manufactured to EN1057:2006 and +A1:2010 Seamless round copper tube, R250 half hard). Maximum working pressure 16.0 bar. Maximum operating temperature 100°C.
‘AF’ range of compression fittings with brass or chrome plated brass bodies for use with copper pipe (manufactured to EN1057). Maximum working pressure 16.0 bar. Maximum working temperature 85˚C
Range of Victaulic rigid couplings (905, H10, H11, H20, H50) for use with plain end HDPE pipe (EN 12201-2), and for product 907, for use with EN 12201-2 HDPE and EN 10217-1 steel pipe. For above and below ground use. Maximum working pressure: SDR7.4 25bar, SDR11 16bar or SDR17 10bar. Maximum operating temperature: Cold water use only.
Range of metric and imperial PVC-U Solvent cement or Threaded fittings for use with PVC-U pressure pipe Class E manufacture to BS EN 1452 Maximum working pressure; 16 Bar Maximum operating temperature; Cold water only
Range of dual flush WC syphons incorporating polypropylene bodies and stainless-steel C-links. Cold water use only
Qmpress Instaboil Range of under counter electric instantaneous water heaters with stainless steel tank and heating element. Open outlet use only. Maximum operating temperature 98°C.
Range of heat interface units providing heating and instantaneous hot water. The central heating and hot water is generated via plate heat exchangers. The central heating circuit contains a pressure relief valve (3.0 bar) and an expansion vessel. Max Temperature & Pressure: Primary Circuit: 6.0 bar at 90°C DHW Circuit: 10.0 bar at 55°C Secondary Circuit 6.0 bar at 90°C
Range of horizontal multistage pumps with stainless steel bodies, diffuser and impellers and EPDM ‘O’-rings. The products incorporate a graphite-SiC-EPDM shaft seal. The products incorporate a drain plug. Maximum working pressure 8.5 bar. 9Maximum operating temperature 80°C.
Range of multistage centrifugal pumps with stainless steel impellers, intermediate chambers, shaft and outer sleeve. The DPV(M/S) models and DPV(S) models can also incorporate an approved check valve cartridge; however, the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum working pressures: Existing models: DPV models 10.0 bar, DPVM models with an oval flange or VME models with integral check valve 16.0 bar, All other DPVM models 25.0 bar. DPV(S) models with an oval flange or DPV(S)(E) models with integral check valve 16.0 bar, All other DPV(S) models and DPH(S)I models 25.0 bar. Maximum operating temperatures: DPHM, DPVE and DPVME models with integral check valve 60°C, all other model variants 100°C.
Range of horizontal multistage pumps with stainless steel bodies, diffuser and impellers and EPDM ‘O’-rings. The products incorporate a graphite-SiC-EPDM shaft seal. The products incorporate a drain plug. Maximum working pressure 8.5 bar. Maximum operating temperature 35°C.
Product Identification | Surface finish | Inlet Dimension | Max Wrk. Pressure | Max Op. Temp. | Marking | Marking Location | All metals in the water pathway are on the 4msi positive list | Headwork | Fixing Type | Spout Outlet | Includes |
---|---|---|---|---|---|---|---|---|---|---|---|
HS183 XXX | VARIOUS | 1/2" BSP | N/A bar | 85 °C | PPI | ON BODY | No | Not applicable | Not Applicable | Not Applicable | |
HS2019 XXX | VARIOUS | 1/2" BSP | N/A bar | 85 °C | PPI | ON BODY | No | Not applicable | Not Applicable | Not Applicable | |
HS2018 XXX | VARIOUS | 1/2" BSP | N/A bar | 85 °C | PPI | ON BODY | No | Not applicable | Not Applicable | Not Applicable | |
HS3013 XXX | VARIOUS | 1/2" BSP | N/A bar | 85 °C | PPI | ON BODY | No | Not applicable | Not Applicable | Not Applicable |
XXX Denotes the following: First, second & third different finishes: Chrome – No suffix, Brushed brass – BGP, PVD Gold – PVD, Brushed Nickel – BN1, Gun Metal – GMG, Matt Black – MBK, Stainless Steel – SS1, Black Chrome – BCP, Titanium – TIB and Antique Bronze – AB1.
Range of shower handsets and headsets with chromium plated plastic bodies. Models P60901 and P61400 have check valves fitted at the inlets however, the complete products have not been fully tested to demonstrate they provide backflow prevention. Maximum working pressure: Open outlet. Maximum operating temperature: 60.0°C.
Range of fixed shower arms, (brass bodies - various finishes) with EPDM O-Rings. Maximum operating temperature: 85°C, open outlet use only.
Page 203 of 207
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.