Range of gate valves with a non-rising spindle with a handwheel operating member or lockshield connection. All models have brass body and brass wedge. For use with copper pipe (manufactured to EN1057). Maximum working pressure 16.0 bar.
Non-metallic materials and components comply with BS6920 at 85°C
Stop valves with a brass body and T-type operating member. Maximum working pressure 16.0 bar.
Non-metallic materials and components comply with BS6920 at 85°C
Range of brass stopcocks. Compression connections, to be used with copper pipe EN1057 only. Maximum working pressure 16.0 bar.
Non-metallic materials and components comply with BS6920 at 85°C
STAD range of balancing valves with brass bodies, PTFE sliding washer and EPDM O-rings. Models are available with or without a drain port. Maximum working pressure 25.0 bar. Maximum operating temperature 100°C.
Range of ultraviolet disinfection units with stainless-steel bodies. Maximum working pressure 16.0 bar. Cold water use only.
'ELECTROLINE ES 1212'. Factory applied, white coloured, two-component, solvent -free epoxy coating. Mix base and hardener in a 2:1 volume ratio and apply as per manufacturer's TDS 'ECL/ TDS / ES1212', issue date '2-Feb-14', version '0'. Cure for 7 days@30°C. For use with water up to 60°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the materials are not covered by the scope of the approval.
‘NMSP2104 M & ER2104A01SM'. The following coatings were added to the approval in March 2025: ER2209A01SC, ER2252A01SC, ER2259A01SC & ER2260A01SC. Factory applied, blue coloured, porcelain (vitreous) enamel coatings. Apply as per manufacturer’s user manual 'PEM 38', edition '01' dated '14/10/2020'. Cure for 5 minutes@840°C. For use with water up to 85°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
‘PMSP5099-M & EP5099D01SC'. Factory applied, blue coloured, porcelain (vitreous) enamel coatings. Apply as per manufacturer’s user manual 'PEM 37', edition '01' dated '14/10/2020'. Cure for 5 minutes@840°C. For use with water up to 85°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'PRIMGREEN® ENDURANCE & Primgreen LAT 12035' primers for use with 'RILSAN® PA11 T BLUE 7444 MAC (16293), PA11 T GREY 5161 MAC (17203), PA11 T WHITE 1488 AC (17219) & PA11 T BLACK 7450 AC (17185)' coatings. Factory applied primers and powder coatings. The piece to be coated is to be pre-heated to 330°C for 10 minutes, the primer and coating applied in accordance with user instructions 'Dircom - 4418E/05.2015/20' and then cured for 10 minutes@330°C. For use with water up to 60°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Sikagard® 1816 (formerly known MasterProtect® 1816)'. Site applied, grey coloured (once applied), two-component Epoxy polysulfide coating. Mix parts A & B in a 78:22 weight ratio and apply coat 1 as per manufacturer’s general method statement ‘MS - AD - Sikagard®-1816-01/2024’ and PDS '020303000000002044 Version 01.01', dated April 2024. Cure coat 1 for 9 hours@25°C. Mix parts A & B in a 78:22 weight ratio and apply coat 2 as per manufacturer’s general method statement ‘MS - AD - Sikagard®-1816-01/2024’ and PDS '020303000000002044 Version 01.01', dated April 2024. Cure coat 2 for 14 days@25°C. For use with water up to 23°C. This material is only approved for the mixing & curing conditions that appear on the approval. If the mix and/or cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
Page 99 of 116
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.