Range of drain off taps incorporating DZR brass bodies, non-rising spindle operating mechanism and EPDM ‘O’-rings and seat washer. FIG 371 range incorporates a lockshield mechanism and the FIG 370 range incorporates a key operated mechanism. Maximum working pressure 16.0 bar. Maximum operating temperature 85°C.
Drain cock elbow incorporating a DZR brass body with EPDM ’O’-rings (ZELB250445 model) or NBR ‘O’-rings (ZELB250446 model added July 2022). Both models are for use with copper pipe (manufactured to BS EN 1057). Maximum working pressures: ZELB250445 model - 10.0 Bar. ZELB250446 - 16.0 bar. Maximum operating temperature 85°C.
Range of wall mounted hose union taps (brass, chrome plated brass or DZR brass body) incorporating a non-rising spindle headwork with a butterfly handle operating member. Maximum working pressure 16.0 bar. Maximum operating temperature 85°C.
Self-closing tap for drinking water fountains (chromium plated brass) with dome type operating member. The spout outlet incorporates a stainless-steel strainer. The product is supplied with a metal back nut. Maximum working pressure 5.0 bar. Cold water use only.
Range of self-closing taps (chromium plated brass) incorporating spring loaded headworks with dome type operating members. The spout outlet of the 9000 model incorporates a plastic flow straightener. The products are supplied with a metal back nut. Maximum working pressure 5.0 bar. Maximum operating temperature 60°C, except for the 9054SA model which is cold water use only.
Self-closing drinking fountain tap (chromium plated brass) with non-concussive headwork operated via a push button. The tap incorporates a metal shroud and is supplied with a metal back nut. Maximum working pressure 10.0 bar. Maximum operating temperature 85°C.
Range of vertical cased and insulated direct and indirect unvented stainless steel hot water storage cylinders. The storage cylinders incorporate an internal air bubble to accommodate the expansion of hot water. The DHW circuit has a factory fitted temperature and pressure relief valve set at 10.0@90˚C. The inlet control group includes a pressure reducing valve set at 3.0 bar, single check valve cartridge (verified by test and suitable for backflow protection against Fluid Category 2) and a expansion valve set at 8.0 bar. The products are supplied with a tundish and a motorised valve to be installed on the primary indirect circuit. Maximum supply pressure to the pressure reducing valve is 12.0 bar. Maximum working pressure of primary circuit is 6.0 bar. Maximum secondary circuit is 9.5 bar. Maximum operating temperature 85°C.
Range of 2, 3 and 4 port manifold assemblies with either DRZ brass or brushed chrome plated brass bodies incorporating screw down isolation valves with dome type operating members. Maximum working pressure 10.0 Bar Maximum operating temperature 85.0°C
Range of air venting valves incorporating an epoxy coated, iron body and a drain point. Maximum working pressure 16.0 bar. Maximum operating temperature 60˚C.
Range of air venting valves incorporating an epoxy coated, iron body and a drain point. Maximum working pressure 16.0 bar. Maximum operating temperature 60˚C.
Page 9 of 101
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.