Shower kit comprising of chrome plated wall mounted shower outlet, shower hose and handset. The inlet incorporates a stainless-steel strainer and an approved check valve cartridge; however, the complete product has not been fully tested to demonstrate it provides backflow protection.
Non-metallic materials and components comply with BS6920 at 60°C
Range of wall mounted shower outlets (various finishes). The inlet incorporates an approved check valve cartridge, however, the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum operating temperature 60°C. Open outlet use only.
Range of shower outlet elbows with chrome plated brass bodies. The inlet incorporates a single check valve cartridge however, the complete product has not been fully tested to demonstrate It provides backflow protection. Open Outlet use only.
Non-metallic materials and components comply with BS6920 at 60°C
Range of wall mounted, overhead shower outlets with brass bodies (chromium plated), EPDM o-rings, fibre gasket and strainer at the shower head inlets. Multiple spray patterns available which is controlled via solenoid valve and a touch sensor. Product incorporates an approved check valve cartridge, however, the complete product has not been fully tested to demonstrate it provides backflow protection. Open outlet use only. Maximum working temperature 60°C.
'Hurricane' range of Indirect and direct unvented storage cylinders consisting of factory fitted single or twin coil circuit with either a primary or solar coil. The secondary circuit is factory fitted with a temperature and pressure relief valve set at 7.0 bar@90˚C. The product is supplied with an inlet control group (safety kit) consisting of a pressure reducing valve adjustable between 2.7 and 3.3 bar, strainer, an expansion relief valve set at 6.0 bar and a check valve cartridge (verified by test - suitable for backflow protection against Fluid Category 2). A tundish and expansion vessel are also provided. Maximum supply pressure to the inlet control group 10.0 bar. Maximum working pressures: Secondary circuit 3.0 bar, Primary Circuit 3.0 bar & Solar circuit 5.5 bar. Maximum operating temperature 65°C.
Page 315 of 559
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.