Range of floor mounted, swivel, bath mixers (brass or stainless-steel bodies - variety of finishes (see models), incorporating ceramic cartridge headworks with single lever operating members. The spout outlets incorporate plastic aerators. The products also incorporate self-cancelling diverters to a shower handset. The diverter outlets incorporate an approved check valve cartridges, however, the complete products have not been fully tested to demonstrate they provide backflow protection. Maximum working pressure 5.0 Bar.
Non-metallic materials and components comply with BS6920 at 60°C
Range of wall mounted brass bodied spout outlets (various finishes, see model) incorporating a plastic aerator. Maximum working pressure 10.0 Bar
Non-metallic materials and components comply with BS6920 at 60°C
Range of longitudinal (EFW) welded stainless steel (Grade 304/304L & 316/316L) pipes. Maximum working pressures: 1¼” sch 10: below ground = 55.0 bar. Above ground = 74.0 bar. 1½” sch 10: below ground = 48.0 bar. Above ground = 64.0 bar. 2” sch 10: below ground = 38.5 bar. Above ground = 51.0 bar. 2½” sch 10: below ground = 34.5 bar. Above ground = 46.0 bar. 3” sch 10: below ground = 28.0 bar. Above ground = 38.0 bar. 4” sch 10: below ground = 22.0 bar. Above ground = 29.0 bar. 5” sch 10: below ground = 19.5 bar. Above ground = 26.0 bar. 6” sch 10: below ground = 16.0 bar. Above ground = 22.0 bar. 8” sch 10: below ground = 14.0 bar. Above ground = 18.0 bar. ½” sch 40 & ¾” sch 40: below ground = 60.0 bar. Above ground = 80.0 bar. 1” sch 40: below ground = 30.0 bar. Above ground = 40.0 bar. 1¼” sch 40 & 1½” sch 40: below ground = 60.0 bar. Above ground = 80.0 bar. 2” sch 40: below ground = 54.5 bar. Above ground = 72.0 bar. 2½” sch 40: below ground = 60.0 bar. Above ground = 80.0 bar. 3” sch 40: below ground = 52.0 bar. Above ground = 69.0 bar. 4” sch 40: below ground = 44 bar. Above ground = 58.0 bar 5” sch 40: below ground = 38.5 bar. Above ground = 51.0 bar. 6” sch 40: below ground = 35.0 bar. Above ground = 46.0 bar. 8” sch 40: below ground = 31.0 bar. Above ground = 41.0 bar. Maximum operating temperature 100°C.
‘Super Speedfit’ range of plastic pushfit fittings (black, light grey, dark grey, white, natural, and red) for use with John Guest LLDPE tubing (blue, black, natural, green, orange, red, white and yellow). Operating parameters: 5/32”, ¼”, 5/16”, 4mm & 6mm = 16.0 bar cold water & 8.0 bar at 65°C. 3/8” = 10.0 bar cold water & 7.0 bar at 65°C. ½” = 10.0 bar cold water & 6.0 bar at 65°C. 8mm, 12mm & 15mm = 10.0bar cold water & 6.0 ba at 65°C. 10mm = 10.0bar cold water & 7.0 bar at 65°C.
Range of ‘Superseal’ and ‘Speedfit’ push-fit fittings with acetal body’s (black or light grey) and NBR ‘O’ rings. For use with John Guest LLDPE tubing (Speedfit port only) and 316 stainless steel tubing manufactured to EN10088 (Superseal push-fit port only). Pipe inserts must be used for the LLDPE tube sizes 3/8” and ½”. Maximum working pressure: See models below. For cold water use only.
Range of air- or water-cooled commercial ice making machines with flow controlled via solenoid valve. Maximum working pressure 5 Bar
Non-metallic materials and components comply with BS6920 at 35°C
Range of commercial air or liquid cooled ice making machines with water controlled via solenoid valve. Maximum working pressure 5.5 Bar COLD WATER USE
Range of water meters with (blue epoxy coated) brass bodies and plastic working chamber. The inlets incorporate a plastic filter. Maximum working pressure 16.0 bar.
Non-metallic materials and components comply with BS6920 at 50°C
‘H5000’ range of helical rotor, bulk water meters with blue epoxy coated cast iron bodies and nitrile `O` rings. Maximum working pressure 16.0 bar. Cold water use only.
Range of water meters with blue epoxy coated ductile iron bodies, plastic measurement chambers and vanes and NBR ‘O’-rings. Maximum working pressure 16.0 bar. Maximum operating temperature 50°C.
Page 354 of 1180
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.