'GCF-SRC'. Factory applied, grey coloured cement mortar. Mix sand, cement and water in a ratio of 4:2:1 and apply as per manufacturer's instructions 'QC-WI-8.1.8, revision 2/0, issue date 30/10/2021'. Cure for 28 days@24°C. For use with water up to 65°C. This material is only approved for the mixing & curing conditions that appear on the approval. If the mix and/or cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Titanseal 989'. Site applied, two-component, grey coloured (once mixed) polyurethane coating. Mix the grey coloured (opaque) base coating with the amber coloured hardener in a 3:1 volume ratio and apply Coat 1 as per manufacturer's application instructions dated '09.03.2018'. Cure for 4 hours@7°C. Mix and apply Coat 2 using the same mix ratio and application instructions and then cure for 14 days@7°C. For use with water up to 23°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the materials are not covered by the scope of the approval.
‘PULRON 101 AQUA’. Factory applied, green coloured polyethylene coating. Apply a single coat (200μm thickness) as per manufacturer's instructions 'ELS.TT.C01.40', 'Rev00', dated '13.06.2023', Cure for 10 minutes at 200°C. Between June 2023 and December 2024, the material was for use with water up to 23°C. Between January 2025 and June 2028, the material is for use with water up to 65°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
Non-metallic materials and components comply with BS6920 at 65°C°C
'Electrocoat EP812 Blue'. Factory applied, blue coloured, two-part epoxy coating consisting of a base and hardener. Mix base and hardener in a volume ratio of 3:1 and apply as per manufacturer's data sheet 'ECL / TDS / EP 812 - BLUE, RAL 5017', issue date '12-Jan-13', version '03', revision date '25-Sept-14'. Cure for 1 hour@60°C followed by 7 days@28°C. For use with water up to 23°C. From March 2024 the material is for use with water up to 60°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mix and/or cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Weberdry epo PW'. Site applied, light grey coloured (once mixed), two-component epoxy coating. Mix Part A (light grey coloured) with Part B (translucent, yellow coloured) in a weight ratio of 100:20. Apply as per manufacturer's TDS 'Edition: 04.23-A'. Cure for 24 hours@25°C. Mix and apply a second coat in the same way and then cure for 14 days@25°C. For use with water up to 23°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mix and/or cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Hyperlast™ 500WP Polyol and Hyperlast™ 500WP prepolymer'. Site applied, grey coloured (once mixed), two-component polyol and prepolymer based coating. Mix Part A (grey liquid) with Part B (amber liquid) in a volume ratio of 1:1 and apply as per manufacturer's 'General Method Statement, DOW WATERPOTABLE 500, Edition 1 07/23'. Cure for 24 hours@7°C. For use with water up to 60°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mix and/or cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Vorastar™ 5342WP Polyol and 'Vorastar™ 5342WP prepolymer'. Site applied, cream coloured (once mixed), two-component urethane based coating. Mix Part A (amber liquid) with Part B (amber liquid) in a volume ratio of 1:1 and apply as per manufacturer's 'General Method Statement, DOW WATERPOTABLE, Edition 1 07/23'. Cure for 24 hours@7°C. For use with water up to 60°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mix and/or cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
`EcoZmart Waterproofing`. Site applied, grey coloured tanking slurry. Mix tanking slurry with water in a 3:1 volume ratio and apply coat 1 as per manufacturer's IFU 'TCOWP001', dated '26/05/2023'. Cure for 24 hours@7°C. Mix tanking slurry with water in a 3:1 volume ratio and apply coat 2, 24 hours after the first coat, as per manufacturer's IFU IFU 'TCOWP001', dated '26/05/2023'. Cure for 14 days@7°C. For use with water up to 23°C. This material is only approved for the mixing & curing conditions that appear on the approval. If the mix and/or cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Al Muftah Sectional Tank Panel'. Light grey coloured, hot press moulded GRP panel. For use with water up to 23°C. From April 2024 the panel is for use with water up to 50°C.
'GPB2, GPB3, GPB4 & GPB6'. White coloured, liquid lubricants. For use with water up to 85°C.
Page 284 of 620
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.