Range of non-rising spindle gate valves with bronze bodies and wedges incorporating PTFE seals and a handwheel type operating member. Maximum working pressure and operating temperature: 16.0 bar @ 65°C. Maximum working pressure and operating temperature: 10.0 bar @ 82°C.
Range of gate valves with brass bodies and gates incorporating hand wheel type operating member. Max working pressure and operating temperatures: 16.0 bar at 65°C. Max working pressure and operating temperatures: 10.0 bar at 82°C.
Range of screw down stop valves with brass bodies and PTFE seals. For use with copper pipe to EN1057. Maximum working pressure 16.0 bar. Maximum operating temperature 65ºC.
Range of combined stop valve and drain off valves with brass bodies and EPDM O-rings. Maximum working pressure 16 Bar Maximum operating temperature 65°C
Screw down stop valves. The 15BSC model has a DZR brass body and a T type operating member. The STAP200009 model has a chrome plated brass body and a dome type operating member. The 15BSC push fit connections are for use with copper pipe (manufactured to BS EN 1057), PB pipe (with inserts) (manufactured to BS EN 7291-2) and PEX pipe (with inserts) (manufactured to BS EN 7291-3). The STAP200009 model has compression connections which are for use with copper pipe (manufactured to BS EN 1057). Maximum working pressure 12.0 bar. Cold water use only.
Range of screw down stop valves with plastic bodies to be used with PEX, MDPE and copper pipe. For above ground use only. Maximum working pressure 16.0 bar, cold water use only.
Cold water inlet control group with a DZR brass body consisting of a pressure reducing valve (with an adjustbale range between 1.5 and 3.5 bar, but factory pre-set at 3.0 bar), which incorporates a stainless steel strainer, and a pressure relief valve (pre-set at 6.0 bar). The product incorporates a single check valve cartridge (verified by test, suitable for backflow protection against Fluid Category 2). The expansion valve is fitted with a rotary type easing gear. Maximum inlet supply pressure 16.0 bar. Cold water use only.
Range of cold water inlet control groups with DZR brass bodies, consisting of a pressure reducing valve, (all models are adjustable between 1.0 and 6.0 bar, but some come pre-set from the factory - see model), a pressure relief valve (set at 6.0 or 8.0 bar - see model) and a single check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2). The pressure relief valve is fitted with a rotary type easing gear. All products for use with copper pipe manufactured to BS EN 1057. Maximum inlet supply pressure 20.0 bar. Cold water use only.
Range of combination valves consisting of an in-line adjustable pressure reducing valve (between 1.5 and 6.0 bar) and a pressure relief valve, with DZR Brass bodies, EPDM `O`-rings and an EPDM diaphragm. CWIC110004 model - Pressure reducing valve pre-set at 3.5 bar and pressure relief valve set at 6.0 bar. CWIC200055 model - Pressure reducing valve pre-set at 3.0 bar and pressure relief valve set at 4.5 bar. The product incorporates a stainless-steel mesh and a check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2). For use with copper pipe (manufactured to BS EN 1057). Maximum supply pressure 16.0 bar. Outlet pressure range 1.5 bar to 6.0 bar (both models). Maximum operating temperature 20°C.
Range of pressure reducing valve assemblies with DZR brass bodies incorporating a spherical valve, a pressure gauge and 2 inline check valve cartridges, verified by test (suitable for backflow protection against Fluid Category 3). Models TVAP250001 & TVAP250005 also incorporate a water meter port. Maximum supply pressure 16 bar. Outlet pressure setting is adjustable in the range 1.5 to 6 bar.
Non-metallic materials and components comply with BS6920 at 65°C
Page 9 of 10
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.