Section Code 2345 : Special combination assemblies.
Back To Directory SectionsExpansion group consisting of a pressure relief valve (set at 6.0 bar), incorporates check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2) and spherical ball valve housed within a DZR brass body. Maximum working pressure 16 bar. Maximum operating temperature 85°C
Cold water inlet control group consisting of a pressure reducing valve, (adjustable between 1.5 and 3.5 bar, but are supplied pre-set from the factory at 3.0 bar) and a pressure relief valve (pre-set at 8.0 bar) housed within a DZR brass body. The product incorporates a single check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2). The pressure relief valve is fitted with a rotary type easing gear. Cold water use only. Maximum inlet supply pressure 16.0 bar.
Cold water inlet control group with a DZR brass body consisting of a pressure reducing valve, (adjustable between 2.7 and 3.3 bar, but factory set at 3.0 bar), a stainless steel strainer and a plastic bodied pressure relief valve (pre-set at 8.0 bar). The product incorporates a single check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2). The pressure relief valve is fitted with a rotary type easing gear. Maximum supply pressure 10.0 bar. Maximum operating temperature 85°C.
Cold water inlet control group with a DZR brass body consisting of a pressure reducing valve (with an adjustbale range between 1.5 and 3.5 bar, but factory pre-set at 3.0 bar), which incorporates a stainless steel strainer, and a pressure relief valve (pre-set at 6.0 bar). The product incorporates a single check valve cartridge (verified by test, suitable for backflow protection against Fluid Category 2). The expansion valve is fitted with a rotary type easing gear. Maximum inlet supply pressure 16.0 bar. Cold water use only.
5 way manifold assembly with a DZR brass body incorporating a pressure reducing valve, with an adjustable outlet pressure range between 1.0 and 6.0 bar and a safety relief valve set at 6.0 bar. The product incorporates an inline single check valve cartridge after the balanced cold take off, verified by test (suitable for backflow protection against Fluid Category 2). Maximum supply pressure 16.0 bar. Maximum operating temperature 40°C
Range of cold-water inlet control groups with DZR brass bodies consisting of an in-line, adjustable pressure reducing valve (PRV) (adjustable in the range of 0.8 bar - 6.0 bar, but factory pre-set at 3.0 or 3.5 bar - see model), strainer and a DZR brass bodied pressure relief valve (SRV) (set at 4.75 bar or 6.0 bar - see model). Products also incorporate an approved single check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2). Maximum supply pressure 16.0 bar. Maximum operating temperature 80°C.
Range of 5 way inlet control group assemblies with a DZR brass body incorporating a pressure reducing valve, with an adjustable outlet pressure range between 2.7 and 3.3bar and a safety relief valve set at 8.0 bar. The product incorporates an inline single check valve cartridge after the balanced cold take off, verified by test (suitable for backflow protection against Fluid Category 2) and strainer on the inlet Maximum supply pressure 10.0 bar. Maximum operating temperature 85°C
Range of cold water inlet control groups with DZR brass bodies, consisting of a pressure reducing valve, (all models are adjustable between 1.0 and 6.0 bar, but some come pre-set from the factory - see model), a pressure relief valve (set at 6.0 or 8.0 bar - see model) and a single check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2). The pressure relief valve is fitted with a rotary type easing gear. All products for use with copper pipe manufactured to BS EN 1057. Maximum inlet supply pressure 20.0 bar. Cold water use only.
Range of inlet control groups with DZR brass bodies incorporating an in-line, adjustable, pressure reducing valve (PRV) (adjustable range ±10% of the factory pre-set value - see model), and a pressure relief valve (SRV) (set at 3.0 bar, 4.5 bar or 6.0 bar - see model). The product incorporates a single check valve cartridge, after the pressure reducing valve, verified by test (suitable for backflow protection against Fluid Category 2). The product also incorporates an approved check valve cartridge on the angled cold water take off point, verified by test (suitable for backflow protection against Fluid Category 2). Maximum supply pressure 10.0 bar. Cold water use only.
Range of thermostatic circulation valves with gunmetal bodies. Maximum working pressure 10.0 bar. Maximum operating temperature 90°C.
Page 1 of 2
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.