Range of ultra-violet disinfection units consisting of a stainless-steel body and quartz tubes with EPDM O rings. Maximum working pressure 16.0 bar. Maximum operating temperature 50.0°C
Range of under-counter or counter-top drinking water dispensers delivering still ambient, still chilled & sparkling water. HygienePlus®. Models incorporate a built-in filter system. The flow is controlled by a solenoid valve which is either operated by a touch or a touch pad. The water is dispensed via a tap arrangement on under-counter versions or an integrated outlet on counter-top versions. The inlets incorporate an approved check valve cartridge assembly however, the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum working pressure 6.0 bar. Cold water use only.
'Jotapipe IL6001 50S'. Factory applied, blue coloured, fusion bonded epoxy coating. Apply as per technical data sheet dated '10 September 2019'. Cure for 15 minutes@230°C. For use with water up to 85°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'EDELPOXY FN 132 Blue'. Factory applied, blue coloured epoxy coating. Apply as per manufacturer's IFU reference 'PC 132' dated 'January 28, 2020'. Cure for 7 days@30°C. For use with water up to 85°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Aixin Powder Coating RAL 5015 Blue'. Factory applied, blue coloured EP coating comprising of base, hardener, pigment, filler and additive agent. The base, hardener, pigment, filler and additive agent were mixed in a 60:12:10:17:1 mass ratio. Cure for 15 minutes@200°C. For use with water up to 85°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the materials are not covered by the scope of the approval.
Page 74 of 2327
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.