Monobloc manifold containing an in-line pressure reducing valve (Adjustment Range between 2.7 and 3.3 bar, but factory pre-set at 3 bar) and a pre-set expansion relief valve (pre-set pressure 6 bar) housed in a DZR brass body with an EPDM rubber diaphragm. The product incorporates also a check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2). Inlets and outlets have compression connections, for use with copper pipe to EN1057. Maximum working pressure 12 bar. Maximum operating temperature 80°C.
'TENAC-C 4590'. White (translucent) coloured, injection moulded acetal material. For use with water up to 85°C.
'RELIBIT 1001 Coating'. Factory applied, black coloured bitumen coating. Apply as per manufacturer's Standard Operating Procedure & Guidelines 'RP/291', '203/2024, Revision 1', dated '1st April 2024'. Cure for 10 hours@35°C. For use with water up to 23°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Ak99,5 - 99,5% Alumina Ceramic'. Ivory coloured, compression moulded and fired Ceramic material. For use with water up to 85°C.
'LM119-1'. Factory applied, white coloured epoxy coating. Apply as per manufacturer's User Instructions 'File no.: LM-001', 'Edition: A', 'Issue date: 2024-JAN.-15th'. Cure for 10 minutes@190°C. For use with water up to 65°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'LARTON G/40 NAT.:0169F1'. Brown coloured, injection moulded PPS material. For use with water up to 85°C.
'3P764921 Pipe Spacer'. White coloured (opaque), injection moulded PP Pipe Spacer. For use with water up to 85°C.
'VL1001P279'. Blue coloured, compression moulded silicone rubber. Shore hardness 60. Tested in-radius size 0.99mm. For use with water up to 65°C.
'Cura External Leak Sealer (Part No: 27813)'. Clear silicone sealant. Apply as per manufacturer's TDS 'Version 1', dated '16/07/2025'. Cure for 96 hours@23°C. For use with water up to 23°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'CarboStop 102/CarboStop 102 ACC'. Site applied, cream coloured (once applied) waterstop. Mix CarboStop 102 resin and CarboStop 102 ACC accelerator in a weight ratio of 20:0.4. Apply and cure as per manufacturer's Application Guide, revision date '19/09/25'. For use with water up to 23°C. This material is for use in concrete reservoirs and similar structures, constructed in accordance with the design criteria of BS EN 1992 with respect to normal frequency of joints. The material has been tested at a reduced surface area to volume ratio of 1000mm² per litre as specified in BS 6920: Part 1. This material is only approved for the mixing & curing conditions that appear on the approval. If the mix and/or cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
Page 408 of 429
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.