T-type mixing valve with a DZR brass body (nickel plated), temperature is controlled by a thermostatic cartridge. For use with copper pipe manufactured to EN1057. Maximum working pressure 5.0 bar. Maximum operating temperature 60°C.
Range of wall mounted, bar type, thermostatic shower blending valves (chromium plated brass), incorporating a ¼ turn ceramic disc headwork controlling the flow with a dome type operating member. The temperature is controlled independently via a thermostatic cartridge with a dome type operating member incorporating a manual override button. Both inlets incorporate a stainless steel strainer and an approved check valve cartridge, however the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum working pressure 10.0 bar. Maximum operating temperature 65°C.
Range of wall mounted, concealed, thermostatic shower valves with brass bodies and trim sets (various finishes - see models). Flow is controlled as follows (for operating members - see model): Single outlet models: ¼ turn ceramic disc headwork. Double Outlet Models without diverter: ¼ turn ceramic disc headworks. Double Outlet Models with diverter: 2-way ceramic disc diverter headwork. Triple Outlet Models with diverter: ¼ turn ceramic disc headwork and a 2-way ceramic disc diverter headwork. The temperature is controlled independently via a thermostatic cartridge with various operating members (see model) which incorporates a manual override button. The inlets incorporate a single check valve cartridge, however, the complete assembly has not been tested to demonstrate it provides backflow protection. Specific models are supplied with a shower hose and handset (see models). Maximum working pressure 5.0 Bar Maximum operating temperature 60°C
Wall mounted bar type thermostatic mixing valve (chromium plated brass) incorporating a ¼ turn ceramic disc headwork controlling the flow with a dome type operating member and a secondary ceramic disc headwork diverting the flow between the overhead shower and hand shower with a single lever operating member. The temperature is controlled independently via a thermostatic mixing cartridge with a dome type operating member that incorporates a manual override button. Both inlets incorporate single check valve cartridges, however, the complete assembly has not been tested to demonstrate it provides backflow protection. The product is supplied with a fixed overhead shower, shower handset and hose. Maximum working pressure 10.0 bar. Maximum operating temperature 60°C.
Wall mounted, concealed, 2-way diverter valve (brass body and chrome trim set) with a single lever operating member. Maximum working pressure 5.0 bar. Maximum operating temperature 65°C.
Manually adjustable pressure reducing valve, which incorporates a DZR brass body and an in-line double check valve assembly on the inlet (verified by test as suitable for backflow protection against Fluid Category 3). The outlet incorporates a shut-off valve. Maximum supply pressure 16.0 bar. Maximum outlet pressure between 1.5 bar and 6.0 bar. Maximum operating temperature 40°C.
Range of 5 way inlet control group assembly incorporating a DZR brass body incorporating a pressure reducing valve, with an adjustable outlet pressure range of either 3.0 bar, 3.5 bar, or 6.0 bar and a safety relief valve set at either 6.0 bar or 8.0bar (depending on model). The product incorporates an inline single check valve cartridge after the balanced cold take off, verified by test (suitable for backflow protection against Fluid Category 2). Maximum supply pressure 10.0 bar. Maximum operating temperature 85°C
Range of adjustable, pilot operated, pressure reducing control valves with black plastic bodies, EPDM diaphragm, EPDM ‘O’-rings and NBR seals. The products are supplied with auxiliary stainless-steel tubing, lever operated spherical valves, integral stainless-steel strainer, pilot valve and a quarter turn ceramic disc valve. Maximum inlet supply pressure 16.0 bar. Maximum outlet pressure 0 - 8.5 bar, 7.0 - 13.5 bar or 12.0 - 16.0 bar (see model). Maximum operating temperature 60°C.
Range of pre-set, spring loaded, angled pressure relief valves with plastic body and EPDM diaphragm. The valves are fitted with rotary type easing gear . For maximum working pressure please refer to model. Maximum operating temperature 99°C.
Range of latching and normally closed (see model) solenoid valves with plastic bodies, NBR diaphragms and ‘O’-rings. Maximum working pressure 10.0 bar. Maximum operating temperature 60°C
Page 136 of 854
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.