Range of adjustable, in-line pressure reducing valves with DZR brass bodies. Adjsutable between 1.0 bar and 5.5 bar outlet pressure. Compression models are for use with copper pipe to EN1057. Maximum inlet supply pressure 16.0 bar. Maximum operating temperature 80°C.
Pressure relief valve pre-set at 6.0 bar, with a brass body and EPDM seat washer. Maximum operating temperature 115°C.
Range of pressure reducing valves with DZR brass bodies, internal stainless steel filter, EPDM ‘O’-rings and diaphragm. Adjustable outlet pressures between 1.0 and 6.0 bar or 1.0 and 12.0 bar (see model). Maximum inlet supply pressure 25.0 bar. Maximum operating temperature 80°C.
Range of inline manually adjustable pressure reducing valves with DZR brass or bronze bodies (see model), EPDM diaphragm, seat washers and ‘O’-rings. Adjustable outlet pressures between 1.0 and 7.0 bar. Maximum inlet supply pressure Art.229.0XX: 40.0 bar, Art.229.1XX: 25.0 bar. Maximum operating temperature 80°C.
Range of in-line, manually adjustable pressure reducing valves with nickel plated DZR brass body. Maximum inlet supply pressure 25 bar. Maximum operating temperature 80°C
The products incorporate two check valve cartridges, verified by test (suitable for backflow protection against Fluid Category 3), a pressure reducing valve adjustable between 1.0 bar and 3.0 bar (but pre-set at 2.5 bar for 523.815 model and 1.4 bar for the 523.816 model). The product incorporates a push type valve which allows water to flow when operated until the required pressure is achieved. There is a drain port below the push valve piston chamber. Compression connections are for use with copper pipe (manufactured to EN 1057). Maximum supply pressure 10.0 bar. Maximum operating temperature 80°C.
Range of in-line, manually adjustable pressure reducing valves with brushed chrome DZR brass bodies. Outlet pressure range: 1.0 - 6.0 bar. Maximum working pressure 16.0 bar. Maximum operating temperature 80°C.
Range of brass bodied automatic air venting valves incorporating a plastic float. Maximum working pressure 10.0 bar. Maximum operating temperature 110°C
Monobloc manifold containing an in-line pressure reducing valve (Adjustment Range between 2.7 and 3.3 bar, but factory pre-set at 3 bar) and a pre-set expansion relief valve (pre-set pressure 6 bar) housed in a DZR brass body with an EPDM rubber diaphragm. The product incorporates also a check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2). Inlets and outlets have compression connections, for use with copper pipe to EN1057. Maximum working pressure 12 bar. Maximum operating temperature 80°C.
Page of 1
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.