Flamco Limited Approvals


#2004317

Airfix D-E range of expansion vessels with white epoxy coated steel bodies and EPDM diaphragm. Maximum working pressure 10.0 bar. Maximum operating temperature 100°C.

Section:
1000 Expansion Vessels
WRAS Approval Number:
2004317
Expiry date:
30/04/2025
Note:
Expansion vessels should be installed in the vertical orientation and located so that the length of the connecting pipework is kept to a minimum
Size:
See model
Marking:
Flamco & logo, model, pressure, capacity, temperature date of manufacture (DD-MM-YY) and other technical information on body.
Installation Requirements:
R001
Model:
Airfix D-E range: Models 100, 200, 300 & 400: 1½” BSP (M). Models 600, 800 & 1000: ” BSP (M).
Approval Holder:
Flamco Limited
Company Name
Flamco Limited
Address
Washway Lane, St. Helens
Postcode
WA10 6PB
Phone
+44 (0) 1744 744 744
General Email
info@flamco.co.uk

View All Listings by this Company
Manufacturer:
Flamco BV
Company Name
Flamco BV
Address
Amersfoortseweg 9 3750 GM Bunschote Nederland
Phone
+31 182 591800 Fax: +31 182 522557
General Email
info@flamco.nl

View All Listings by this Company

Print This Approval


#2009016

Range of cylindrical expansion vessels incorporating butyl rubber diaphragms. The products are supplied with an Airfix TD T piece. Maximum working pressure of model Airfix D 35 litre is 8.0 bar. All other models have a maximum working pressure of 10.0 bar. Maximum operating temperature 100°C.

Section:
1000 Expansion Vessels
WRAS Approval Number:
2009016
Expiry date:
30/09/2025
Note:
Expansion vessels should be installed in the vertical orientation and located so as to minimise the length of any connecting pipework. This product has not been tested or approved for anti-legionella claims made by the approval holder.
Size:
¾” BSP (F) x ¾” BSP (F) x ¾” BSP (F) tee piece connection
Marking:
Airfix, Flamco and technical information on adhesive label on body.
Installation Requirements:
R001
Model:
Airfix D 8 litre, 12 litre, 18 litre, 25 litre & 35 litre.
Approval Holder:
Flamco Limited
Company Name
Flamco Limited
Address
Washway Lane, St. Helens
Postcode
WA10 6PB
Phone
+44 (0) 1744 744 744
General Email
info@flamco.co.uk

View All Listings by this Company
Manufacturer:
Flamco BV
Company Name
Flamco BV
Address
Amersfoortseweg 9 3750 GM Bunschote Nederland
Phone
+31 182 591800 Fax: +31 182 522557
General Email
info@flamco.nl

View All Listings by this Company

Print This Approval


#2203331

Permanent filling/ pressurisation device for primary heating and chilled water closed circuits in domestic and non-domestic premises. The mains and closed circuit system pressures are continuously checked by two pressure sensors and their differential monitored by microprocessors. In the event of a fall in system pressure, and only if the mains pressure is adequate, a solenoid valve operates to allow water into the system. At all other times a second solenoid valve drains the fill chamber to waste, via tundish (meeting the requirements of an air gap to drain), and allowing air to be admitted via an automatic air vent to create an atmospheric disconnection across the transfer chamber. Maximum working pressure 6.0 Bar. Cold water use only.

Section:
1530 Miscellaneous Fittings
WRAS Approval Number:
2203331
Expiry date:
31/03/2027
Note:
Suitable for backflow protection up to fluid category 3. Consult your water supplier prior to installation
Size:
½” BSP (M)
Marking:
Flamco on front case.
Installation Requirements:
R001
Model:
Flexfiller Direct G4.
Approval Holder:
Flamco Limited
Company Name
Flamco Limited
Address
Washway Lane, St. Helens
Postcode
WA10 6PB
Phone
+44 (0) 1744 744 744
General Email
info@flamco.co.uk

View All Listings by this Company
Manufacturer:
Flamco Limited
Company Name
Flamco Limited
Address
Washway Lane, St. Helens
Postcode
WA10 6PB
Phone
+44 (0) 1744 744 744
General Email
info@flamco.co.uk

View All Listings by this Company

Print This Approval


#2206803

Range of pressure reducing valves with DZR brass bodies adjustable between 1.0 and 6.0 bar. The valves incorporate a stainless steel strainer. Maximum supply pressure 25.0 bar or 16.0 bar (see model). Maximum operating temperature 80°C.

Section:
2200 Valves
Section Subtitle:
Pressure reducing.
WRAS Approval Number:
2206803
Expiry date:
30/04/2027
Size:
SEE MODEL
Marking:
Flamco, DN, Size, CR, flow arrow and date of manufacturer (MMYY) on body Flamco on operating member
Installation Requirements:
R001 R120
Model:
25.0 bar inlet pressure: 27460 – ½” BSP (M) x ½” BSP (M) 27461 – ¾” BSP (M) x ¾” BSP (M) 27462 – 1” BSP (M) x 1” BSP (M) 16.0 bar inlet pressure: 27466 – 15mm compression x 15mm compression, 27467 – 22mm compression x 22mm compression & 27468 – 28mm compression x 28mm compression.
Approval Holder:
Flamco Limited
Company Name
Flamco Limited
Address
Washway Lane, St. Helens
Postcode
WA10 6PB
Phone
+44 (0) 1744 744 744
General Email
info@flamco.co.uk

View All Listings by this Company

Print This Approval


#2205807

Range of pressure reducing valves with DZR brass bodies, internal stainless steel filter, EPDM ‘O’-rings and diaphragm. Adjustable outlet pressures between 1.0 and 6.0 bar Maximum inlet supply pressure 25.0 bar. Maximum operating temperature 80°C.

Section:
2200 Valves
Section Subtitle:
Pressure reducing.
WRAS Approval Number:
2205807
Expiry date:
31/05/2027
Size:
SEE MODEL
Marking:
FLAMCO, size, DN, flow arrow, CR and date of manufacturer (MM.YY) on body. FLAMCO on operating member
Installation Requirements:
R001 R120
Model:
Adjustable between 1.0-6.0 bar: 27463: 1 ¼” BSP (M) Union, 27464: 1 ½” BSP (M) Union, 27465: 2” BSP (M) Union.
Approval Holder:
Flamco Limited
Company Name
Flamco Limited
Address
Washway Lane, St. Helens
Postcode
WA10 6PB
Phone
+44 (0) 1744 744 744
General Email
info@flamco.co.uk

View All Listings by this Company

Print This Approval


#2207063

Range of expansion vessels with butyl membranes. Maximum working pressure 8.0, 10.0, 16.0 or 20.0 bar (please refer to model). Maximum operating temperature 70 or 100°C (please refer to model).

Section:
1000 Expansion Vessels
WRAS Approval Number:
2207063
Expiry date:
31/07/2027
Note:
Expansion vessels should be installed in the vertical orientation and located so as to minimise the length of any connecting pipework.
Size:
Please refer to model.
Marking:
Flamco, Airfix, model, capacity, maximum operating pressure and other technical information on adhesive label on body.
Installation Requirements:
R001
Model:
AIRFIX P 35, AIRFIX P 50, AIRFIX P 60, AIRFIX P 80, AIRFIX P 100 & AIRFIX P 150 (35, 50, 60, 80, 100 & 150 Litres) Vertical: 10.0 Bar, 100°C, 1” BSP (M). AIRFIX P 200, AIRFIX P 300 & AIRFIX P 500 (200, 300, 450 & 500 Litres) Vertical: 10.0 Bar, 100°C, 1 ¼” BSP (M). AIRFIX P 50 HAIRFIX 60 H, AIRFIX P 80 HAIRFIX P 100 H & AIRFIX P 150 H (50, 60, 80, 100 & 150 Litres) Horizontal: 10.0 Bar, 100°C, 1” BSP (M). AIRFIX P 200 H, AIRFIX P 300 H & AIRFIX P 500 H (200, 300 & 500 Litres) Horizontal: 10.0 Bar, 100°C, 1 ¼” BSP (M). AIRFIX P 2 (2 Litres): 10.0 Bar, 100°C, ½” BSP (M). AIRFIX P 3 & AIRFIX P 5 (3 & 5 Litres): 10.0 Bar, 100°C, ¾” BSP (M). AIRFIX P 8, AIRFIX P 12 & AIRFIX P 16 (8, 12 & 16 Litres): 10.0 Bar, 100°C, ¾” BSP (M). AIRFIX P 18 & AIRFIX P 24 (18 & 24 Litres): 10.0 Bar, 100°C, 1” BSP (M). AIRFIX P 24 H (24 Litres) Horizontal: 8.0 Bar, 100°C, 1” BSP (M).
Approval Holder:
Flamco Limited
Company Name
Flamco Limited
Address
Washway Lane, St. Helens
Postcode
WA10 6PB
Phone
+44 (0) 1744 744 744
General Email
info@flamco.co.uk

View All Listings by this Company

Print This Approval


#2310378

Range of shock arrestors with stainless steel bodies and EPDM diaphragm. Maximum working pressure 10 bar. Maximum operating temperature 70°C

Section:
1000 Expansion Vessels
WRAS Approval Number:
2310378
Expiry date:
31/10/2028
Size:
½” BSP(M).
Marking:
Flamco, Flexofit on body.
Installation Requirements:
R001
Model:
Flexofit. Flexofit without cap
Approval Holder:
Flamco Limited
Company Name
Flamco Limited
Address
Washway Lane, St. Helens
Postcode
WA10 6PB
Phone
+44 (0) 1744 744 744
General Email
info@flamco.co.uk

View All Listings by this Company
Manufacturer:
Flamco Limited
Company Name
Flamco Limited
Address
Washway Lane, St. Helens
Postcode
WA10 6PB
Phone
+44 (0) 1744 744 744
General Email
info@flamco.co.uk

View All Listings by this Company

Print This Approval


#2310115

Range of expansion vessels with epoxy coated steel bodies and EPDM diaphragms. Maximum working pressure 8.0 or 10.0 bar (please refer to model). Maximum operating temperature 70°C or 100°C (please refer to model).

Section:
1000 Expansion Vessels
WRAS Approval Number:
2310115
Expiry date:
31/10/2028
Note:
Expansion vessels should be installed in the vertical orientation and located so as to minimise the length of any connecting pipework.
Size:
2” or 2 ½” BSP (F)
Marking:
Flamco, model, pressure, capacity and other technical information on adhesive label on body.
Installation Requirements:
R001
Model:
Maximum working pressure 10.0 bar. Maximum operating temperature 70°C: AIRFIX P 750, AIRFIX P 1000 & AIRFIX P 1500. Maximum working pressure 8.0 bar. Maximum operating temperature 100°C: AIRFIX P 750 (diam 750)
Approval Holder:
Flamco Limited
Company Name
Flamco Limited
Address
Washway Lane, St. Helens
Postcode
WA10 6PB
Phone
+44 (0) 1744 744 744
General Email
info@flamco.co.uk

View All Listings by this Company

Print This Approval


#240988018

Range of expansion vessels with white epoxy coated steel bodies and butyl diaphragm. Please refer to model for maximum working pressures. Maximum operating temperature 70°C. Maximum working pressure 10.0 bar (all except two models), 8.0 bar (24749 & 24809 only).

Section:
1000 Expansion Vessels
WRAS Approval Number:
240988018
Basis of Compliance:
Tested to regulators Specification Test Code Sheets
Expiry date:
30/09/2029
Size:
¾” BSP (M).
Marking:
Airfix, Flamco, pressure/temperature, date and time of manufacture (time = hour/min/sec) (date = DD/MM/YY), CE Marking & technical information on adhesive label on body.
Installation Requirements:
R001
Model:
24259 - Airfix A 8 litre - Drinkwater exp. Vessel 8 litre with pre charge 4 bar, 24348 / 24349 - Airfix A 12 litre - Drinkwater exp. Vessel 12 litre with pre charge 3 / 4 bar, 24458 / 24460 / 24459Airfix A 18 litre - Drinkwater exp. Vessel 18 litre with pre charge 3 / 3.5 / 4 bar, 24558 / 24559Airfix A 25 litre - Drinkwater exp. Vessel 25 litre with pre charge 3 / 4 bar, 24659 - Airfix A 35 litre - Drinkwater exp. Vessel 35 litre with pre charge 4 bar, 24749 - Airfix A 50 litre - Drinkwater exp. Vessel 50 litre with pre charge 4 bar, 24809 - Airfix A 80 litre - Drinkwater exp. Vessel 80 litre with pre charge 4 bar.
Approval Holder:
Flamco Limited
Company Name
Flamco Limited
Address
Washway Lane, St. Helens
Postcode
WA10 6PB
Phone
+44 (0) 1744 744 744
General Email
info@flamco.co.uk

View All Listings by this Company

Print This Approval


Show Per Page
5102050Show All

Back To Directory Sections

Page of 1

We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.