Backflow Prevention Devices

Section Code 0009 : SCHEDULE 2 - Section 6.2 - Type AB - Air gap with weir overflow.

Back To Directory Sections

#2010039

Rainwater top up cistern with flow controlled by solenoid valve and discharged via a type `AB` airgap (verified by test - suitable for backflow protection against fluid category 5). Product also incorporates a stop valve, a flow restrictor and a float valve on the inlet. Maximum working pressure 10.0 bar. Cold water use only.

Section:
0009 Backflow Prevention Devices
Section Subtitle:
SCHEDULE 2 - Section 6.2 - Type AB - Air gap with weir overflow.
WRAS Approval Number:
2010039
Expiry date:
31/10/2025
Size:
15mm push fit
Marking:
Rain Direct on front panel. Rainwater Harvesting, model, serial number and other product info on adhesive label inside panel.
Installation Requirements:
R001 R415 R574
Model:
RainDirector RD01
Manufacturer:
Rainwater Harvesting Ltd.
Company Name
Rainwater Harvesting Ltd.
Address
Unit A Harrier PArk Orton Southgate Peterborough
Postcode
PE2 6YQ
Phone
01733 405102

View All Listings by this Company

Print This Approval


#2105320

Standpipe assembly break tank with a Type ‘AB’ air gap (verified by test – suitable for backflow protection against fluid category 5) mounted to the top of the standpipe body. The tank is filled via a compact float valve and has two screened weir slots. Water is then supplied by gravity from the break tank to the hose outlet below. Flow is activated via a spherical valve located behind a lockable panel. In addition to the isolation valve, the product incorporates a single check valve assembly (suitable for backflow protection against Fluid Category 2) prior to the spherical valve and an in-line ‘Y’ pattern strainer after it. The spherical valve includes a drain plug to allow for draining. Insulation is provided up to the drain point. Maximum working pressure 10.0 bar. Cold water use only.

Section:
0009 Backflow Prevention Devices
Section Subtitle:
SCHEDULE 2 - Section 6.2 - Type AB - Air gap with weir overflow.
WRAS Approval Number:
2105320
Expiry date:
31/05/2026
Note:
The MDPE pipe manufactured to BS EN 12201-2:2011 noted under size is not supplied or included under the scope of this approval.
Size:
20mm, 25mm or 32mm compression (for use with MDPE pipe manufactured to BS EN 12201-2:2011 only).
Marking:
Arrow valve, product code, manuafcturers website and tel no. on adhesive label on front cover.
Installation Requirements:
R001 R415 R430 R511
Model:
SPFC5X20, SPFC5X25, SPFC5X32.
Manufacturer:
Arrow Valves Ltd
Company Name
Arrow Valves Ltd
Address
York House Northbridge Road Berkhamsted Hertfordshire
Postcode
HP4 1TA
Country
Herts
Phone
01442 823 123

View All Listings by this Company

Print This Approval


#2109040

Type ‘AB’ air gap assembly (verified by test - suitable for backflow protection against Fluid Category 5) with flow controlled via a solenoid valve. Supplied with EPDM inlet hoses that incorporate a single check valve cartridge, however the check valve has not been fully tested to demonstrate it provides backflow protection. Max working pressure 6.0 bar. Maximum operating temperature 60ºC.

Section:
0009 Backflow Prevention Devices
Section Subtitle:
SCHEDULE 2 - Section 6.2 - Type AB - Air gap with weir overflow.
WRAS Approval Number:
2109040
Expiry date:
30/09/2026
Size:
¾” BSP (F)
Marking:
Winterhalter and model on adhesive label on body.
Installation Requirements:
R001 R150 R574
Model:
70014626
Factor:
Winterhalter Gastronom GmbH
Company Name
Winterhalter Gastronom GmbH
Address
Commercial Dishwashing Systems, Tettnanger Strasse 77, 88074 Meckenbeuren
Country
Germany
Phone
0049 (0) 7542 402 0

View All Listings by this Company

Print This Approval


#2209317

Range of pressurisation units with flow controlled by a float operated valve and discharged via a type `AB` airgap (verified by test - suitable for backflow protection against fluid category 5). The inlets incorporate stainless steel strainers, flow restrictors and spherical isolation valves. Maximum working pressure 10.0 bar. Cold water use only.

Section:
0009 Backflow Prevention Devices
Section Subtitle:
SCHEDULE 2 - Section 6.2 - Type AB - Air gap with weir overflow.
WRAS Approval Number:
2209317
Expiry date:
30/09/2027
Note:
To supply non-wholesome water systems only.
Size:
15mm compression.
Marking:
Arrow Valves, size, model and product info on data label on front casing.
Installation Requirements:
R001 R415 R574
Model:
Dose & Fill DF15 & Midi-Fill Digital MFD15.
Manufacturer:
Arrow Valves Ltd
Company Name
Arrow Valves Ltd
Address
York House Northbridge Road Berkhamsted Hertfordshire
Postcode
HP4 1TA
Country
Herts
Phone
01442 823 123

View All Listings by this Company

Print This Approval


#2302800

‘Type `AB` airgap (verified by test - suitable for backflow protection against fluid category 5) incorporating a float operated valve controlling the flow. The inlet hose incorporates an isolation valve. Maximum working pressure 10.0 bar. Cold water use only.

Section:
0009 Backflow Prevention Devices
Section Subtitle:
SCHEDULE 2 - Section 6.2 - Type AB - Air gap with weir overflow.
WRAS Approval Number:
2302800
Expiry date:
29/02/2028
Note:
This appliance incorporates a Fluid Category 5 backflow prevention device.
Size:
Stainless-steel braided EPDM lined flexible hose assembly with 15mm push fit connection.
Marking:
Arrow Valves, Tel No, website, model, fluid catergory 5 protection, and break tank with Type AB Airgap on adhesive label on drip tray.
Installation Requirements:
R001 R574
Model:
AB18
Manufacturer:
Arrow Valves Ltd
Company Name
Arrow Valves Ltd
Address
York House Northbridge Road Berkhamsted Hertfordshire
Postcode
HP4 1TA
Country
Herts
Phone
01442 823 123

View All Listings by this Company

Print This Approval



Back To Directory Sections

Page 2 of 3

We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.