Section Code 2010 : Shower valve(s) with thermostatic temperature control
Back To Directory SectionsRange of T-type thermostatic mixing valves with DZR brass bodies. Temperature is pre-set under a fixed cap. The inlet adaptors incorporate single check valve cartridges (verified by test, suitable for backflow protection against Fluid Category 2) and stainless-steel strainers. The inlet adaptors for models DT400MX15CP & DT400MX22CP are 90° elbows instead of straight adaptors and incorporate additional integral spherical valves. Maximum working pressure 10.0 Bar. Maximum operating temperature 85.0°C.
Range of wall mounted concealed electronically controlled thermostatic shower mixers, incorporating plastic solenoid valves to control the flow to various outlets activated via a remote actuator. The temperature is controlled via two transducers housed within the concealed box. The products incorporate approved single check valve cartridges, however, the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum operating pressure: 6.0 bar. Maximum operating temperature: 65°C
Range of wall mounted bar type thermostatic shower valves (brass bodies – various finishes) incorporating ceramic disc headwork which controls the flow to 2 outlets with dome type operating members. Temperature is controlled independently via a thermostatic cartridge with dome type operating member which incorporates a manual override button. Both inlets incorporate an approved check valve cartridge however, the complete product has not been fully tested to demonstrate it provides backflow protection. Supplied with an optional flow regulator. Maximum working pressure 10.0 bar. Maximum operating temperature 65°C
Range of wall mounted thermostatic blending valves, (brass bodies - various finishes) incorporating a single sequential headwork, controlling the flow and the temperature and a manually operated diverter to the shower outlets The inlet on the shower handset incorporates an approved single check valve cartridge, however, the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum working pressure 10.0 bar. Maximum operating temperature 60°C
Range of T-Type thermostatic mixing valve (chromium plated brass). For use with copper pipe to BS EN1057. Maximum working pressure; 10 Bar Maximum operating temperature 85°C.
Page 93 of 128
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.