Range of copper, bronze or DZR brass capillary solder ring fittings for use with copper pipe (manufactured to EN 1057). Maximum working pressure and operating temperatures: 8-28mm: 25.0 bar @ 30°C, 16.0 bar @ 100°C. 35-54mm: 25.0 bar @ 30°C, 16.0 bar @ 65°C and 10.0 bar @ 100°C.
‘SR’ range of capillary solder ring copper fittings for use with copper tube EN1057, for above ground use only. Maximum working pressure: 25.0 bar. Maximum operating temperature: 85°C.
‘SharkBite’ range of brass push fit fittings incorporating an EPDM ‘O’-ring. For use with the following pipes: JG Speedfit Layflat Polybutylene Barrier Pipe (JG BPB pipe manufactured to BS EN 7291-2:2010), 'BPEX' Barrier Pipe (JG BPEX pipe manufactured to BS EN 7291-3:2010), Polybutylene barrier pipe (manufactured to BS EN 7291-2:2010), PEX barrier pipe (manufactured to BS EN 7291-3:2010) and Copper pipe (manufactured to BS EN1057:2006). Maximum working pressures and operating temperatures: When used with Polybutylene barrier pipes (manufactured to BS EN 7291-2:2010) and PEX barrier pipes (manufactured to BS EN 7291-3:2010): 12.5 bar, cold water use only. 6.0 bar @ 95°C. When used with copper pipe (manufactured to BS EN1057:2006): 10mm sizes: Maximum working pressure 16.0 bar. Cold water use only. Maximum working pressure 10.0 bar. Maximum operating temperature 95°C. 15-22mm sizes: Maximum working pressure 20.0 bar. Cold water use only. Maximum working pressure 16.0 bar. Maximum operating temperature 95°C. 28mm size added April 2024: Maximum working pressure 20.0 bar. Cold water use only. Maximum working pressure 16.0 bar. Maximum operating temperature 95°C.
Range of Redman fittings with mild steel bodies (polyamide coating) for use with Puriton II PE-AL-PE barrier pipe - For above and below ground and cold-water use. Jointing is achieved by hydraulic compression. Maximum working pressures: 12.5 Bar for 63mm SDR 11 PE80 pipe system, 10.0 Bar for 90mm to 180mm SDR 17 PE100 pipe system, 16.0 bar for 90mm to 180mm SDR 11 PE100 pipe system. Cold water use only.
Range of end feed copper fittings for use with copper tube manufactured to EN1057, for above ground use only. Maximum working pressure 25.0 bar. Maximum operating temperature 85℃.
Page 577 of 802
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.