Directory Search Results

Print List

#2012120

WC flushing cistern incorporating a side entry compact type float operated inlet valve providing a Type AG air gap with a dual flush drop valve for full flush volumes of up to 6 litres and a reduced flush of up to 4 litres. The cistern is operated by a manual push button and incorporates a servicing valve on the inlet supply. Maximum working pressure 10.0 bar. Cold water use only.

Section:
2035 Cistern - Flushing
Section Subtitle:
Incorporating Type AG air gap, providing fluid category 3 backflow protection. Suitable for use in a WC suite. Additional tests will need to be performed if required to demonstrate Type AUK1 air gap.
WRAS Approval Number:
2012120
Size:
½” BSP (M)
Marking:
BAGNODESIGN and model number on cistern body. 6 litre line inside cistern
Installation Requirements:
R001 R556
Expiry date:
31/12/2025
Model:
BDS-K210-A01-ESG6 UNIVERAL FRAMED 820 CONCEALED CISTERN FOR WALL HUNG WC BDS-K210-D03-ESG3 CONCEALED CISTERN FOR BACK TO WALL WC

Approval Holder:
BAGNODESIGN
Company Name
BAGNODESIGN
Address
UNIT 1 OAKWELL PARK TRADING ESTATE BIRSTALL
Postcode
WF17 9LU

View All Listings by this Company

Print This Approval


#250201703

Concealed BS EN 14055: 2018 WC flushing cistern incorporating a side entry compact type float operated inlet valve providing a type `AB` airgap (verified by test - suitable for backflow protection against fluid category 5) with a dual or single flush pneumatic drop valve capable of full flush volumes of up to 6 litres and a reduced flush of 4 litres. The cistern can be operated by touch free electronic or manual push button / push plate options. The supply hose incorporates a servicing valve. Maximum working pressure 10.0 bar. Cold water use only.

Section:
2034 Cistern - Flushing
Section Subtitle:
Incorporating Type AB air gap, providing fluid category 5 backflow protection. Suitable for use in a WC suite.
WRAS Approval Number:
250201703
Basis of Compliance:
Tested to regulators Specification Test Code Sheets
Size:
½” BSP Male or 15mm Push-fit Inlet connection.
Marking:
Front service cover is marked with Dudley logo moulding Top of outlet drop valve marked TD Front nut of inlet valve marked DUDLEY
Installation Requirements:
R001 R574 R581
Expiry date:
31/01/2030
Model:
Vantage Concealed Cistern (Category 5).

Approval Holder:
Thomas Dudley Limited
Company Name
Thomas Dudley Limited
Postcode
DY1 4SJ
Country
United Kingdom
Phone
0121 530 7053
General Email
jcresswell@thomasdudley.co.uk

View All Listings by this Company
Manufacturer:
Thomas Dudley Limited
Company Name
Thomas Dudley Limited
Postcode
DY1 4SJ
Country
United Kingdom
Phone
0121 530 7053
General Email
jcresswell@thomasdudley.co.uk

View All Listings by this Company

Print This Approval


#250102714

Range of flow sensors with plastic bodies. Maximum working pressure 16.0 bar. Maximum operating temperature 100°C.

Section:
0009 Backflow Prevention Devices
Section Subtitle:
SCHEDULE 2 - Section 6.2 - Type AB - Air gap with weir overflow.
WRAS Approval Number:
250102714
Basis of Compliance:
Tested to regulators Specification Test Code Sheets
Size:
DN6 (½” BSP M), DN8 (½” BSP M), DN10 (¾” BSP M), DN15 (¾” BSP M), DN20, (1” BSP M) & DN25 (1¼” BSP M).
Marking:
Huba control, model code, connection size, date of manufacture (DD/MM/YY) and other technical data on face of body. Flow arrow and DN on body.
Installation Requirements:
R001
Expiry date:
31/01/2030
Model:
Vortex Flow Sensor Type 240.
Product Images

Manufacturer:
Huba Control AG
Company Name
Huba Control AG
Address
Industriestrasse 17, CH-5436 Wurenlos, Switzerland

View All Listings by this Company

Print This Approval


#250104711

DC type pipe interrupter with a permanent atmospheric vent (DZR brass body) incorporating a flow regulator at the inlet and brass shroud. Maximum working pressure 6.0 bar. Cold water use only.

Section:
0014 Backflow Prevention Devices
Section Subtitle:
SCHEDULE 2 - Section 6.2. Type DC - Pipe interrupter with permanent atmosphere vent. The device must be fitted with the lowest point of the air aperture not less than 150mm above the free discharge point, or spillover level of an appliance, and have no valve, flow restrictor or tap on its outlet.
WRAS Approval Number:
250104711
Basis of Compliance:
Tested to regulators Specification Test Code Sheets
Size:
¾” BSP (F)
Marking:
Cistermiser on shroud, DC pipe interrupter and CR mark stamped on body.
Installation Requirements:
R001 R165
Expiry date:
31/01/2030
Model:
DWC/10
Product Images

Approval Holder:
Cistermiser Ltd
Company Name
Cistermiser Ltd
Address
Unit 1 Woodley Park Estate, 59/69 Reading Road Woodley
Postcode
RG5 3AN
Country
United Kingdom
General Email
jake.felstead@cistermiser.co.uk

View All Listings by this Company

Print This Approval


#250102709

Spring loaded, resilient trim, in-line check valve cartridge with NBR & EPDM ‘O’-rings, plastic guide, stem and body. For insertion into pipes or fittings with specifically dimensioned bores. Maximum working pressure 8.6 Bar. Maximum operating temperature 60°C.

Section:
0026 Backflow Prevention Devices
Section Subtitle:
SCHEDULE 2 - Section 6.2 Check Valve Cartridge. The cartridges listed in this section are for factory installation only and are not suitable for on-site installation.
WRAS Approval Number:
250102709
Basis of Compliance:
Tested to regulators Specification Test Code Sheets
Size:
12.8mm OD
Marking:
SOLEX on body.
Installation Requirements:
R001
Expiry date:
31/01/2030
Model:
T10193
Product Images

Manufacturer:
Xiamen Solex High-Tech Industries Co., Ltd.
Company Name
Xiamen Solex High-Tech Industries Co., Ltd.
Address
No. 298 Yangguang Road West, Haicang District, Xiamen, Fujian Province, 361022
Country
China

View All Listings by this Company

Print This Approval



Back To Directory Sections

Page 2086 of 2219

We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.