Franklin Electric SRL Approvals


#2006001

Range of vertical multistage pumps with stainless-steel bodies, stainless-steel impellers, intermediate chambers, shaft and outer sleeve. Cold water use only. Maximum working pressure 12.0 bar.

Section:
1610 Pumps
Section Subtitle:
Wholesome water use.
WRAS Approval Number:
2006001
Expiry date:
30/06/2025
Size:
EM3/XX & EM5/XX models: DG threaded Rp 1 ¼”. TG oval DN32 flanged. RG threaded Rp 1 ¼”. EM5/XX DG threaded Rp 1 ¼” EM5/XX TG oval DN32 EM5/XX RG threaded Rp 1 ¼” Size added January 2021: EM9/XX DG threaded Rp 1 ½” EM9/XX TG oval DN40 EM9/XX RG threaded Rp 1 ½”
Marking:
Franklin Electric logo & product information on adhesive label on body and Models added January 2021 also include: WRAS
Installation Requirements:
R001 R415
Model:
EM3/XX XGFFF AA E1 EM5/XX XGFFF AA E1 Models added January 2021: EM9/XX XGFFF AA E1 Where: XX - no. of stages from 2 up to 9 XG - type of ports and bottom casing material as follows: DG - in line threaded connections and cast-iron bottom casing TG - in line oval connections and cast-iron bottom casing RG - top-bottom threaded connections and cast-iron bottom casing FFF - kW motor size AA - motor connection and frequency as follows: M5 - single phase and 50Hz T5 - three phase and 50Hz M6 - single phase and 60Hz T6 - three phase and 60Hz E1 - mechanical seal type
Factor:
Franklin Electric SRL
Company Name
Franklin Electric SRL
Address
Via Asolo 7 Dueville Vicenza 36031
Phone
+39 0444 360366
General Email
info.it@fele.com

View All Listings by this Company

Print This Approval


#2104008

Range of horizontal self-priming multistage pumps with stainless steel bodies, stainless steel impellers, shaft and outer sleeve. Maximum working pressure 10.0 Bar Maximum operating temperatures: EH Three phase models 85°C, EH Single phase models 55.0°C and EHsp models 35°C.

Section:
1610 Pumps
Section Subtitle:
Wholesome water use.
WRAS Approval Number:
2104008
Expiry date:
30/04/2026
Size:
EH models: 1 ¼” BSP (F) – 2” BSP (F) EHsp models: 1” BSP (F)
Marking:
Data label showing Franklin electric S.r.l, model number, PMAX and other technical info on body. WRAS label on body. Max temperature on adhesive label on body.
Installation Requirements:
R001 R415
Model:
Horizontal/Self-Priming Multi-Stage Pumps: EH 3/XX A KKK MM EN B C D. EH 5/XX A KKK MM EN B C D. EH 9/XX A KKK MM EN B C D. EH 15/XX A KKK MM EN B C D. EH 20/XX A KKK MM EN B C D. EHsp 3/XX A KKK MM EN B C D. EHsp 5/XX A KKK MM EN B C D. Where: EH = Standard model. EHsp = Self-priming model. 3/5/9/15/20 = rated power [m³/h]. XX = no. of stages (50 Hz single phase): 2 to 9 for EH 3 & 5; 2 to 6 for EH 9; 2 to 3 for EH 15; 2 for EH 20; 4 & 5 stages for EHsp 3 & 5. (50 Hz three phase): 2 to 9 for EH 3 & 5; 2 to 8 for EH 9; 2 to 7 for EH 15; 2 to 5 for EH 20; 4 & 5 stages for EHsp 3 & 5. (60 Hz single phase): 2 to 7 for EH 3; 2 to 5 for EH 5; 2 to 3 for EH 9; 3 to 5 for EHsp 3 & 5. (60 Hz three phase): 2 to 7 for EH 3 & 5; 2 to 5 for EH 9; 2 to 4 for EH 15; 2 to 3 for EH 20; 3 to 5 for EHsp 3 & 5. A = Pump material: “I” for AISI 304 (All the versions) and “N” for AISI 316 (not available for “EHsp” versions). KKK = Motor power (kW x 10). MM = motor connection and frequency as follows: M5 = single phase and 50Hz T5 = three phase and 50Hz M6 = single phase and 60Hz T6 = three phase and 60Hz EN = Type of mechanical seal: E0 or E1 or E2 for EH 3/5/9 models. E1 or E2 for EH 15/20 models. E0 for EHsp models. B = “No load” - standard version, D - sealing disc with plug. C = “No load” - standard version, A - cable with plug, S = without condensate drain plugs. D = motor efficiency class.
Factor:
Franklin Electric SRL
Company Name
Franklin Electric SRL
Address
Via Asolo 7 Dueville Vicenza 36031
Phone
+39 0444 360366
General Email
info.it@fele.com

View All Listings by this Company

Print This Approval


#2110066

Range of vertical multistage pumps with stainless-steel bodies, stainless-steel impellers, shaft and outer sleeve. Maximum working pressures: T (oval flange): 16.0 bar. V (Victaullic & grooved), C (clamp flanges) & F (round flange) versions: 26.0 bar. Maximum operating temperature 100°C.

Section:
1610 Pumps
Section Subtitle:
Wholesome water use.
WRAS Approval Number:
2110066
Expiry date:
31/10/2026
Size:
EV1-EV3 & 1VR-3VR models - F (round flange) versions: DN25. EV6-EV20 & 6VR-20VR models - F (round flange) versions: DN32-50. EV1-EV20 & 1VR-20VR models - T (oval flange), V (Victaullic - EV; Grooved - VR), C (clamp flanges) & F (round flange) versions: DN32-50.
Marking:
Franklin Electric, model name, date of production (DD/MM/YYYY), pressure, temperature and other technical information on data plate on body.
Installation Requirements:
R001 R415
Model:
EV and VR ranges. Code example (EV range): EV 20 /15 A B C D E F G H J K L M N PMP/A. Where: EV = Pump model EV (EV = E-Tech “brand”). 20 = Rated flow [m³/h] (varies: 1-20). /15 = No. of stages/impellers. (See model and stages below for more detail). A = No. of trimmed impellers, if "Empty" = none. B = Flange type: "F" - round; "T" - oval; "V" - Victaulic; "C" - clamp. C = Materials: "I" - (AISI304/EN1.4301); "N" (AISI316/EN1.4401). D = Motor power (kW x 10). E = Frequency: "5" - 50Hz; "6" - 60Hz. F = No. of motor poles: "Empty" - 2 poles; "4" - 4 poles. G = Motor type: "Empty" - without motor, "T" - 3-phase; "M" - 1-phase. H = Mechanical Seal: "Empty" - standard version (EV1-EV20 & 1VR-20VR versions only). J = Type of mechanical Seal: E1 (SiC-Carbon Graphite-EPDM) or E2 (SiC-SiC-EPDM). K = "Empty" - standard version, "H" - high pressure. L = "Empty" - standard version, "P" - passivated. M = "Empty" - standard version N = "Empty" - no motor, “IE..” motor efficiency class. PMP/A = cold formed pump casing. Code example (VR range): 3 VR0700 A B C X-XXXX. Where: 3 = Rated flow [m³/h] (varies: 1-20). VR = Pump model (VR = FPS “brand”). 07 = No. of stages/impellers. (See model and stages below for more detail). 00 = Impeller trim: 00 = no trim, A1 = 1A (one trimmed impeller), A2 = 2A (two trimmed impellers). A = Materials: "H" - (AISI304/EN 1.4301); "N" (AISI316/EN 1.4401). B = Flange type: "F" - round; "T" - oval; "V" - Grooved (Victaullic); "C" - clamp. C = Mechanical Seal: “1” - QBE; “2” - QQE. X-XXXX = Combination of numbers and letter relating to frame, speed, motor and electronics (does not affect water pathways). Last two digits can be empty for versions without a motor. Minimum and maximum number of stages (please note the oval flange models have a lower maximum, this is included in brackets as follows [15] to denote 15 stages): EV1/1VR: stage from 2 to 37 [23] (50Hz) and from 2 to 25 [15] (60Hz); EV3/3VR: stage from 2 to 33 [21] (50Hz) and from 2 to 23 [14] (60Hz); EV6/6VR: stage from 2 to 36 [21] (50Hz) and from 2 to 23 [14] (60Hz); EV10/10VR: stage from 2 to 24 [15] (50Hz) and from 2 to 17 [10] (60Hz); EV15/15VR: stage from 1 to 17 [10] (50Hz) and from 1 to 12 [10] (60Hz); EV20/20VR: stage from 1 to 17 [10] (50Hz) and from 1 to 10 [7] (60Hz).
Factor:
Franklin Electric SRL
Company Name
Franklin Electric SRL
Address
Via Asolo 7 Dueville Vicenza 36031
Phone
+39 0444 360366
General Email
info.it@fele.com

View All Listings by this Company

Print This Approval


#2303041

Range of multistage pumps (VL and CL series) and submersible pumps (VN, CN, ES and CS series) with stainless steel bodies and impellers and NBR gaskets and ‘O’-rings. Maximum working pressure 15.0 bar (VL and CL series pumps only).

Section:
1610 Pumps
Section Subtitle:
Wholesome water use.
WRAS Approval Number:
2303041
Expiry date:
31/03/2028
Note:
VN, CN, ES and CS series submersible pumps: The level control assembly (cable and level control) are not covered under the scope of this approval. These pumps are also open outlet use only.
Size:
VL and CL series: 1 ¼” Female BSP inlet x 1 ½” Female BSP outlet. VN and CN series: 1 ¼” Female BSP outlet - 2" Female BSP outlet. ES and CS series: 1 ¼” Female BSP outlet.
Marking:
Franklin electric Srl logo, WRAS, model no., serial no., pressure and date of manufacture (DD/MM/YYY) on body.
Installation Requirements:
R001 R415
Model:
VNx1/xx2 Ixxx3 x4x5x6 Nx7 x8Bx9x10x11Nx12 D, x1CN/xx2 Ixxx3 x4x5x6 Nx7 x8Bx9x10x11Nx12 D, VLx1/xx2 Ixxx3 x4x5x6 Nx7 x8Bx9x10x11Nx12 D, x1CL/xx2 Ixxx3 x4x5x6 Nx7 x8Bx9x10x11Nx12 D, ESx1/xx2 Ixxx3 x4x5x6 Nx7 x8Bx9x10x11Nx12 D, x1CS/xx2 Ixxx3 x4x5x6 Nx7 x8Bx9x10x11Nx12 D. Where: VN, CN, VL, CL, ES, CS = Series name. VN/VL/ES series “E-TECH” brand CN/CL/CS Series “FPS” brand x1 = Nominal Flow: 3, 5, or 9. (9 is not available on ES and CS models) xx2 = number of impellers: 2 to 10 (VN/CN & VL/CL models), 2 to 8 (ES/CS models), depending on Nominal Flow and Frequency. I = Material: St/Steel 1.4301 (AISI304). xxx3 = Motor Power (kW x 10): 005, 007, 009, 011… x4 = Supply (no phase): T (three phase), M (single phase). x5 = Frequency (Hz): 5 (50 Hz), or 6 (60 Hz). x6 = Motor Configuration: L (Bi-phase, 90° single-phase), D (Three-phase, triangle), or Y (Three-phase, star). N = Mechanical seal elastomer: N = NBR. x7 = Mechanical Seal surface: 1 (Graphite / Silicon Carbide), or 2 (Silicon Carbide). x8 = Float Switch: 0 (without). B = Cable type: B (Blue). x9 = Cable size: A (4G1), B (4G1.5), C (3G1), or D (3G1.5). x10 = Cable length: O: 20m - VN/CN and ES/CS models, E: 5m - VL/CS models. x11 = Control Panel (not in contact with liquid): 0 (without), or 1 (connected - VN/CN models only). N = Nude terminal (not in contact with liquid). x12 = Option (only on VN/CN models) - Discharge head (”): Empty (1¼” Nickel plated brass), I (1¼” inox), or J (2” inox). D = Drinking water approved.
Factor:
Franklin Electric SRL
Company Name
Franklin Electric SRL
Address
Via Asolo 7 Dueville Vicenza 36031
Phone
+39 0444 360366
General Email
info.it@fele.com

View All Listings by this Company

Print This Approval


#2305073

Range of vertical multistage pumps with either stainless-steel bodies (“N” versions) or cast iron bodies with a black electrodeposition coating (“G” versions), stainless-steel impellers, shaft and outer sleeve. Maximum working pressure: EV30, EV45, 30VR & 45VR models - 32.0 bar, EV65, EV95, 65VR & 95VR models - 25.0 bar. Max operating temperature: Stainless steel (“N” versions) - 100°C. Cast iron (“G” versions) - Cold water use only.

Section:
1610 Pumps
Section Subtitle:
Wholesome water use.
WRAS Approval Number:
2305073
Expiry date:
31/05/2028
Size:
DN65 - DN100
Marking:
Franklin electric S.r.l logo, serial number, model number, date of manufacture (DD/MM/YYYY) and pressure on data plate on body.
Installation Requirements:
R001 R415
Model:
EV and VR ranges. Code example (EV range): EV 30 /13 A B C D E F G H J K L M N. Where: EV = Pump model EV (EV = E-Tech “brand”). 30 = Rated flow [m³/h] (varies: 30-95). /13 = No. of stages/impellers. (See model and stages below for more detail). A = No. of trimmed impellers, if "Empty" = none. B = Flange type: "F" - round. C = Materials: "G" - (cast iron/Stainless steel); "N" - (AISI316/EN1.4401). D = Motor power (kW x 10). E = Motor type: “Vacuum” (pump without motor), "T" - 3-phase; "M" - 1-phase. F = Frequency: "5" - 50Hz; "6" - 60Hz. G = No. of motor poles: "Empty" - 2 poles; "4" - 4 poles. H = Mechanical Seal: "B" (balanced). J = Elastomeric and mechanical seal material: E1 (SiC-Carbon Graphite-EPDM) or E2 (SiC-SiC-EPDM). K = “IE…” motor efficiency class IEC60034-30, where applicable, “Vacuum” (pump without motor). L = “Vacuum” standard version,“M” (oversized motor). M = "Vacuum” - standard version. N = Motor voltage, “Vacuum” (pump without motor). EV30: stage from 1 to 13 (50Hz) and from 1-1A to 8 (60Hz); EV45: stage from 1-1A to 13-2A (50Hz) and from 1-1A to 7 (60Hz); EV65: stage from 1-1A to 8 (50hz) and from 1-1A to 5-1A(60 hz); EV95: stage from 1-1A to 6 (50Hz) and from 1-1A to 4-2A (60Hz). Code example (VR range): 30 VR0700 A B C X-XXXX. Where: 30 = Rated flow [m³/h] (varies: 30-95). VR = Pump model (VR = FPS “brand”). 07 = No. of stages/impellers. (See model and stages below for more detail). 00 = Impeller trim: 00 = no trim, A1 = 1A (one trimmed impeller), A2 = 2A (two trimmed impellers). A = Materials: "G" - (cast iron/304SS); "N" - (AISI316/EN 1.4401). B = Flange type: "F" - round. C = Mechanical Seal: “A” - (BQBE, BE1); “B” - (BQQE, BE2). X-XXXX = Combination of numbers and letter relating to frame, speed, motor and electronics (does not affect water pathways). Last two digits can be empty for versions without a motor. 30VR: stage from 1 to 13 (50Hz) and from 1-1A to 8 (60Hz); 45VR: stage from 1-1A to 13-2A (50Hz) and from 1-1A to 7 (60Hz); 65VR: stage from 1-1A to 8 (50hz) and from 1-1A to 5-1A (60Hz); 95VR: stage from 1-1A to 6 (50Hz) and from 1-1A to 4-2A (60Hz).
Manufacturer:
Franklin Electric SRL
Company Name
Franklin Electric SRL
Address
Via Asolo 7 Dueville Vicenza 36031
Phone
+39 0444 360366

View All Listings by this Company

Print This Approval


#2104082

Range of horizontal self-priming multistage pumps with stainless steel bodies, stainless steel impellers, shaft and outer sleeve. Maximum working pressure 10.0 Bar Maximum operating temperatures: MH Three phase models 85°C, MH Single phase models 55.0°C and EH sp models 35°C.

Section:
1610 Pumps
Section Subtitle:
Wholesome water use.
WRAS Approval Number:
2104082
Expiry date:
30/04/2026
Size:
EH models: 1 ¼” BSP (F) – 2” BSP (F) EHsp models: 1” BSP (F)
Marking:
Data label showing Franklin electric S.r.l, model number, PMAX and other technical info on body. WRAS label on body. Max temperature on adhesive label on body.
Installation Requirements:
R001 R415
Model:
Horizontal Multi-Stage Pumps : 3 MH A XX Z-MM EN 5 MH A XX Z-MM EN 9 MH A XX Z-MM EN 15 MH A XX Z-MM EN 20 MH A XX Z-MM EN Where: A= Pump material: “EMPTY” for AISI 304 and “N” for AISI 316; XX= n. of stages ( 50 Hz single phase): - from 2 to 9 for EH 3 & 5; - from 2 to 6 for EH 9; - from 2 to 3 for EH 15; - 2 for EH 20; n. of stages ( 50 Hz three phase): - from 2 to 9 for EH 3 & 5; - from 2 to 8 for EH 9; - from 2 to 7 for EH 15; - from 2 to 5 for EH 20; n. of stages ( 60 Hz single phase): - from 2 to 7 for EH 3; - from 2 to 5 for EH 5; - from 2 to 3 for EH 9; - No EH 15&20 60Hz single phase; n. of stages ( 60 Hz three phase): - from 2 to 7 for EH 3 & 5; - from 2 to 5 for EH 9; - from 2 to 4 for EH 15; - from 2 to 3 for EH 20; Z=Connection Type: “B” for “Rp” and “P” for “NPT”; MM=motor connection and frequency as follows: 5M=single phase and 50Hz 5T=three phase and 50Hz 6M=single phase and 60Hz 6T=three phase and 60Hz EN= Type of mechanical seal: “E0 – E1 – E2” for EH 3/5/9 ; “E1 – E2” for EH 15/20
Factor:
Franklin Electric SRL
Company Name
Franklin Electric SRL
Address
Via Asolo 7 Dueville Vicenza 36031
Phone
+39 0444 360366
General Email
info.it@fele.com

View All Listings by this Company

Print This Approval


Show Per Page
5102050Show All

Back To Directory Sections

Page of 1

We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.