Dutypoint Ltd. Approvals


#2111366

Range of cold water in tank booster sets incorporating an ‘AG’ air gap, consisting of a GRP water storage cistern incorporating a float operated inlet valve, with a copper float and submersible pump or pumps (depending on model). The products incorporate an externally mounted stainless-steel manifold with servicing valve(s), expansion vessel, pressure gauge and a digital control panel. The pumps are connected to the external components via a discharge assembly of internal pipework including an in-line non-verifiable single check valve assembly (suitable for backflow prevention of Fluid Category 2). Maximum working pressure 10.0 bar. Cold water use only.

Section:
1610 Pumps
Section Subtitle:
Wholesome water use.
WRAS Approval Number:
2111366
Note:
These cisterns are not suitable for water for domestic purposes unless they are so modified and installed as to comply in all respects with Schedule 2. Section 7, Paragraph 4, of the Water Supply (Water Fittings) Regulations 1999. The products incorporate a Fluid Category 3 air gap arrangement.
Size:
1" BSP (M)
Marking:
Fluid Water, Stuart Turner or Flowtech, address, product ref, capacity, job ref and contact information on adhesive label on tank body. Fluid Water or Stuart Turner, model, year of manufacturer and serial no on control box.
Installation Requirements:
R001 R280 R415
Expiry date:
30/11/2026
Proviso:
If implemented, the overflow and warning pipe discharge to drain must be via a type `AA` `AB` or `AD` airgap in accordance with EN 1717.
Model:
IT-A-V-B-C-D-E-F-G-AG Where: IT = Product range name (In Tank). A = Number of pumps (1,2, or 3 pumps). V = Variable speed. B = Maximum flow (l/min per pump - 80 or 120l/min). C = Maximum head (m per Pump, e.g. 60). D = Controller type (MAB). E = Power input (T = 3 Phase – M = 1Phase). F = Vessel Capacity (8 = 8 litre, 24= 24 litre). G = Tank size (Nominal capacity in litres - 250-3000). AG = ‘AG’ air gap. Example: IT-3V-8060-MAB-M/24-1000-AG In Tank booster set with 3 pumps, variable speed, 80l/min max. flow and 60m max. head, MAB controller, 1 phase, 24 litre expansion vessel, 1000 litre capacity with an AG air gap. Model added October 2025: IN - A - B - C - D - E - F IN = Product range name A = number of pumps (1,2, or 3 pumps) B = Maximum flow (per pump) C = Maximum Head (per pump) D = Tank capacity E = Voltage F = Controller Type Example: IN3-8060-1000-M-MAB • IN = product range • A = 3 pumps • B = 80 l/min max flow • C = 60m max head • D = 1000L nominal capacity • E – 1 phase 230v • F = MAB control panel

Approval Holder:
Dutypoint Ltd.
Company Name
Dutypoint Ltd.
Address
Unit A, Quedgeley West Business Park, Hardwicke, Gloucester
Postcode
GL2 4PA
Phone
01452313334
General Email
austin.hill@dutypoint.com

View All Listings by this Company

Print This Approval


#2110123

Range of vertical multistage pumps with stainless-steel bodies, stainless-steel impellers, shaft and outer sleeve. Maximum working pressures: T (oval flange): 16.0 bar. V (Victaullic & grooved), C (clamp flanges) & F (round flange) versions: 26.0 bar. Maximum operating temperature 100°C.

Section:
1610 Pumps
Section Subtitle:
Wholesome water use.
WRAS Approval Number:
2110123
Size:
TPX1-TPX3 models - F (round flange) versions: DN25. TPX5-TPX20 models - F (round flange) versions: DN32-50. TPX1-TPX20 models - T (oval flange), V (Victaullic - EV; Grooved - VR), C (clamp flanges) & F (round flange) versions: DN32-50.
Marking:
Dutypoint, date of production (DD/MM/YYYY), pressure, temperature and other technical information on data plate on body.
Installation Requirements:
R001 R415
Expiry date:
31/10/2026
Model:
TPX1, TPX3, TPX5, TPX10, TPX15 & TPX20 Range of vertical multistage pumps Code example (TPX range): TPX 20 /15 A B C D E F G H J K L M N PMP/A. Where: TPX = Pump model TPX. 20 = Rated flow [m³/h] (varies: 1-20). /15 = No. of stages/impellers. (See model and stages below for more detail). A = No. of trimmed impellers, if "Empty" = none. B = Flange type: "F" - round; "T" - oval; "V" - Victaulic; "C" - clamp. C = Materials: "I" - (AISI304/EN1.4301); "N" (AISI316/EN1.4401). D = Motor power (kW x 10). E = Frequency: "5" - 50Hz; "6" - 60Hz. F = No. of motor poles: "Empty" - 2 poles; "4" - 4 poles. G = Motor type: "Empty" - without motor, "T" - 3-phase; "M" - 1-phase. H = Mechanical Seal: "Empty" - standard version. J = Type of mechanical Seal: E1 (SiC-Carbon Graphite-EPDM) or E2 (SiC-SiC-EPDM). K = "Empty" - standard version, "H" - high pressure. L = "Empty" - standard version, "P" - passivated. M = "Empty" - standard version N = "Empty" - no motor, “IE..” motor efficiency class. PMP/A = cold formed pump casing. Minimum and maximum number of stages (please note the oval flange models have a lower maximum, this is included in brackets as follows [15] to denote 15 stages): TPX1: stage from 2 to 37 [23] (50Hz) and from 2 to 25 [15] (60Hz); TPX3: stage from 2 to 33 [21] (50Hz) and from 2 to 23 [14] (60Hz); TPX5: stage from 2 to 36 [21] (50Hz) and from 2 to 23 [14] (60Hz); TPX10: stage from 2 to 24 [15] (50Hz) and from 2 to 17 [10] (60Hz); TPX15: stage from 1 to 17 [10] (50Hz) and from 1 to 12 [10] (60Hz); TPX20: stage from 1 to 17 [10] (50Hz) and from 1 to 10 [7] (60Hz).

Approval Holder:
Dutypoint Ltd.
Company Name
Dutypoint Ltd.
Address
Unit A, Quedgeley West Business Park, Hardwicke, Gloucester
Postcode
GL2 4PA
Phone
01452313334
General Email
austin.hill@dutypoint.com

View All Listings by this Company

Print This Approval


#2304317

Range of cold water supply booster sets, consisting of between 2 & 4 pumps, modular stainless steel manifold system, servicing valve, non-return valve (not suitable for backflow protection) and an expansion vessel. Maximum working pressure 10.0 bar or 16.0 bar (identified on adhesive label on expansion vessel) Cold water use only.

Section:
1610 Pumps
Section Subtitle:
Wholesome water use.
WRAS Approval Number:
2304317
Size:
DN50 to DN150
Marking:
Dutypoint Ltd. model, serial number and other technical information on adhesive label on base.
Installation Requirements:
R001 R415
Expiry date:
30/04/2028
Model:
VT2-05-xxxx VT2-10-xxxx VT2-15-xxxx VT2-20-xxxx VT3-05-xxxx VT4-05-xxxx VT3-10-xxxx VT3-15-xxxx VT3-20-xxxx VT4-10-xxxx VT4-15-xxxx VT4-20-xxxx Example of model: VT2-05-015T xxxx on end of model codes above denotes all motor size and type. Range: VT. Number of Pumps: 2. Nominal flow rate: (m³/hr) 05. Motor kW: (without decimal)15 (1.5kw). Voltage: (T=400/3/50 M=230/1/50) T

Approval Holder:
Dutypoint Ltd.
Company Name
Dutypoint Ltd.
Address
Unit A, Quedgeley West Business Park, Hardwicke, Gloucester
Postcode
GL2 4PA
Phone
01452313334
General Email
austin.hill@dutypoint.com

View All Listings by this Company
Manufacturer:
Dutypoint Ltd.
Company Name
Dutypoint Ltd.
Address
Unit A, Quedgeley West Business Park, Hardwicke, Gloucester
Postcode
GL2 4PA
Phone
01452313334
General Email
austin.hill@dutypoint.com

View All Listings by this Company

Print This Approval


#2312802

Range of cold water supply booster sets, incorporating stainless steel manifold system connecting 2 or 3 wholesome water pumps. The set also includes spherical valves, non-return valves (not intended or suitable for backflow protection) and expansion vessels. Maximum working pressure 10.0 bar. Cold water supply only.

Section:
1610 Pumps
Section Subtitle:
Wholesome water use.
WRAS Approval Number:
2312802
Size:
DN80 inlet x DN80 outlet flanged connections. DN50 inlet x DN65 outlet flanged connections.
Marking:
Dutypoint, model, serial number and technical information on adhesive label on base plate.
Installation Requirements:
R001 R415
Expiry date:
31/12/2028
Model:
DN50 Discharge Versions: Twin pump units: FR/VR2-03, FR/VR2-05, FR/VR2-10. Triple pump units: FR/VR3-03, FR/VR3-05, FR/VR3-10. DN80 Discharge Versions: Twin pump units: FR/VR2-15, FR/VR2-22. Triple pump units: FR/VR3-15, FR/VR3-22. The model is suffixed with two numbers to denote motor size and ‘LHT’.

Approval Holder:
Dutypoint Ltd.
Company Name
Dutypoint Ltd.
Address
Unit A, Quedgeley West Business Park, Hardwicke, Gloucester
Postcode
GL2 4PA
Phone
01452313334
General Email
austin.hill@dutypoint.com

View All Listings by this Company
Manufacturer:
Dutypoint Ltd.
Company Name
Dutypoint Ltd.
Address
Unit A, Quedgeley West Business Park, Hardwicke, Gloucester
Postcode
GL2 4PA
Phone
01452313334
General Email
austin.hill@dutypoint.com

View All Listings by this Company

Print This Approval


#2311337

Range of break tanks and pump sets incorporating a Type AB airgap (verified by test - suitable for backflow protection against fluid category 5). Maximum working pressure 10 bar. Cold water use only.

Section:
0009 Backflow Prevention Devices
Section Subtitle:
SCHEDULE 2 - Section 6.2 - Type AB - Air gap with weir overflow.
WRAS Approval Number:
2311337
Note:
To supply non-wholesome water systems only.
Size:
½” BSP (F) 1” BSP (F) 1 ¼” BSP (F)
Marking:
Dutypoint, address, Model, Serial No and pressure rating on adhesive label on panel.
Installation Requirements:
R001 R415 R574
Expiry date:
1/12/2028
Model:
VQ1 VQ2 FQ1** FC1 Example of Model Number: VQ1-05-015M Range: VQ (other options are FQ, FC & VC) Number of Pumps: 1 Nominal Flow: 05 (m3hr) Motor kw (without decimal): 015 (1.5kw) Voltage: M (T=400/3/50 M=230/1/50) *Where 16Bar outlet pressure is required, the only component changed is the pressure vessel. ** the only difference between VQ1 and FQ1 and the FC1 and the VC1 is the electrical control type.

Approval Holder:
Dutypoint Ltd.
Company Name
Dutypoint Ltd.
Address
Unit A, Quedgeley West Business Park, Hardwicke, Gloucester
Postcode
GL2 4PA
Phone
01452313334
General Email
austin.hill@dutypoint.com

View All Listings by this Company
Manufacturer:
Dutypoint Ltd.
Company Name
Dutypoint Ltd.
Address
Unit A, Quedgeley West Business Park, Hardwicke, Gloucester
Postcode
GL2 4PA
Phone
01452313334
General Email
austin.hill@dutypoint.com

View All Listings by this Company

Print This Approval



Back To Directory Sections

Page 1 of 3

We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.