Advance Appliances Ltd. Approvals


#1911074

Range of Advance Appliance stainless steel indirect and direct unvented hot water storage cylinders. The secondary circuit is factory fitted with a temperature and pressure relief valve (7.0 bar and 95°C). The product is fitted with a safety kit which comprises of a manifold, check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2) strainer, an expansion relief valve set at 6.0 bar and a pressure reducing valve set at 3.0 bar. A tundish and expansion vessel also comes supplied. Maximum working pressure: Secondary circuit 6.0 bar. Primary circuit 10.0 bar Maximum operating temperature 85°C

Section:
1890 Unvented Heating Apparatus
WRAS Approval Number:
1911074
Expiry date:
30/11/2024
Size:
22mm compression (manifold). 22mm Stub connection (hot outlet). 22mm Stub connection (secondary return). 22mm Stub connection (coil 1). 32mm Stub connection (coil 2). The above sizes on the approval to be modified to the below: 22mm or 28mm compression connection (manifold) secondary inlet, 22mm or 28mm stub connection secondary outlet 22mm stub or ½”F BSP secondary return 22mm stub connections coil1 inlet and outlet 28mm or 32mm stub connections cold inlet and outlet
Marking:
ADVANCE APPLIANCES, part number and technical information including capacity and pressure on adhesive label on body
Installation Requirements:
R001 R140 R360 R530
Proviso:
WRAS Approval - Solar heating system components. “Compliance with the relevant requirements of the Water Supply (Water Fittings) Regulations 1999 has been assessed for this product only as a component of a heating system. If it is to be installed a s part of a system using solar energy or ground - or air - source heat pumps for pre-heating water which is to be used as domestic hot water, the Water Fittings Regulation place a legal duty on the installer and user to ensure that the installation and operation of the complete system prevents contamination of domestic hot water by Legionella bacteria, which can grow in water stored at temperatures between 20˚C and 45˚C. Where disinfection by heating is relied on to meet this obligation, information on minimum conditions for thermal disinfection of legionella bacteria can be found on the WRAS website - www.wras.co.uk
Model:
Advance Appliances- Heat Pump- single coil HP 135/ 150/215/ 255/ 305 HPL 255/ 305/ 400/ 500 Advance Appliances- Heat Pump - twin coil HPS 215/ 255/ 305 HPSL 305/ 400/ 500 Advance Appliances- Buffer Store - BFS 80/ 150/ 215/ 255/ 305/ 500
Factor:
Advance Appliances Ltd.
Company Name
Advance Appliances Ltd.
Address
Unit 4 Coppice Side Industrial Estate, Brownhills, Walsall
Postcode
WS8 7EX

View All Listings by this Company

Print This Approval


#2007084

Advance Appliance ranges of direct, indirect, solar direct and solar indirect stainless steel insulated unvented hot water storage cylinders with internal expansion. The DHW circuit consists of a temperature and pressure relief valve set at 7.0 bar 95°C, an inlet manifold consisting of an in-line pressure reducing valve adjustable between 2.7 & 3.3 bar (but factory set @ 3.0 bar), an approved check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2), a pre-set expansion relief valve set at 6.0 bar and a strainer. The product is supplied with a tundish. Maximum supply pressure to pressure reducing valve is 10.0 bar. Maximum working pressure Primary circuit 6.0 bar. Maximum working pressure Secondary circuit 5.5 bar. Maximum operating temperature 85˚C.

Section:
1890 Unvented Heating Apparatus
WRAS Approval Number:
2007084
Expiry date:
31/07/2025
Note:
All solar models must be installed in accordance with this proviso: WRAS Approval - Solar heating system components. “Compliance with the relevant requirements of the Water Supply (Water Fittings) Regulations 1999 has been assessed for this product only as a component of a heating system. If it is to be installed as part of a system using solar energy or ground- or air- source heat pumps for pre-heating water which is to be used as domestic hot water, the Water Fittings Regulations place a legal duty on the installer and user to ensure that the installation and operation of the complete system prevents contamination of domestic hot water by Legionella bacteria, which can grow in water stored at temperatures between 20°c and 45°C.
Size:
See model
Marking:
Adhesive label on side of cylinder with Advance Appliances model, address and technical information including temperature, capacity and pressure.
Installation Requirements:
R001 R140 R360
Model:
Advances Appliances Indirect - single coil ipp 175 Advance Appliances Indirect- single coil ipp 250
Factor:
Advance Appliances Ltd.
Company Name
Advance Appliances Ltd.
Address
Unit 4 Coppice Side Industrial Estate, Brownhills, Walsall
Postcode
WS8 7EX

View All Listings by this Company

Print This Approval


Show Per Page
5102050Show All

Back To Directory Sections

Page of 1

We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.