Heaters

Section Code 1360 : Electric instantaneous, mains fed, closed outlet. Heat retained in instantaneous water heaters will cause expansion of water after closure of draw-off taps and valves. Provision for expansion of water must be made to accommodate excess pressure within the system. Particular care is required where check valves are positioned, or loose jumper valves are thought to be upstream of the heater.

Back To Directory Sections

#2003355

Electric instantaneous main fed water heaters with stainless steel bodies, EPDM O-rings, silicone seal (40132212 model only), and fibre gaskets. The heaters are supplied with an inlet safety control group consisting of a pressure reducing valve (adjustable between 2.7 and 3.3 bar), pre-set expansion relief valve set at 6.0 bar, a check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2) and an expansion vessel. They are also supplied with a stainless steel braided PEX lined flexible hose assembly incorporating ½” and ⅜” captive nut end connections, and ⅜” BSP (M) brass equal tee for installation prior to the inlet safety control group. The outlet arrangement on the 40132212 model only combines the near boiling water outlet and cold inlet supply via a thermostatic mixing valve, as well as a separate outlet for near boiling water. The outlet arrangement of the 40132312 model supplies near boiling water. The products are supplied with a tundish for installation on the outlet of the safety relief valve. Maximum inlet supply pressure to inlet safety control group 10.0 bar. Maximum working pressure 5.5 bar. Cold supply (inlet). Maximum operating temperature 99°C (water heater and near boiling outlet both models), 90°C (for hot water outlet via thermostatic mixing valve 40132212 model only).

Section:
1360 Heaters
Section Subtitle:
Electric instantaneous, mains fed, closed outlet. Heat retained in instantaneous water heaters will cause expansion of water after closure of draw-off taps and valves. Provision for expansion of water must be made to accommodate excess pressure within the system. Particular care is required where check valves are positioned, or loose jumper valves are thought to be upstream of the heater.
WRAS Approval Number:
2003355
Expiry date:
31/03/2025
Note:
Expansion vessels should be installed in the vertical orientation and located so that the length of the connecting pipework is kept to a minimum. Discharge to drain must be via a type `AA`, `AB` or `AD` airgap, or in accordance with EN1717.
Size:
⅜” BSP (M) (to tee piece). Stainless steel braided PEX lined flexible hose assembly incorporating ½” captive nut end connection (to boiler unit).
Marking:
HotSpot logo, serial number and date of manufacture YYWW followed by a unique number, e.g. 1923001. (19 = 2019, 23 = week 23, 001 = unique production no.) on adhesive label on body.
Installation Requirements:
R001 R007 R009 R511
Model:
40132312 Hotspot Titanium 4L boiler. 40132212 Hotspot Titanium 8L boiler.
Approval Holder:
HotSpot Titanium UK Ltd
Company Name
HotSpot Titanium UK Ltd
Address
90 Rockingham Street Sheffield
Postcode
S1 4EB

View All Listings by this Company
Manufacturer:
Inventum Industrial BV and Inventum Technologies BV
Company Name
Inventum Industrial BV and Inventum Technologies BV
Address

View All Listings by this Company

Print This Approval


#2007344

Range of ‘HYCO’ electric instantaneous water heaters with plastic bodies, NBR and silicone ‘O’-rings. The inlet of model IN96T incorporates a plastic strainer. Maximum working pressure 7.5 bar. Maximum operating temperature 60°C.

Section:
1360 Heaters
Section Subtitle:
Electric instantaneous, mains fed, closed outlet. Heat retained in instantaneous water heaters will cause expansion of water after closure of draw-off taps and valves. Provision for expansion of water must be made to accommodate excess pressure within the system. Particular care is required where check valves are positioned, or loose jumper valves are thought to be upstream of the heater.
WRAS Approval Number:
2007344
Expiry date:
31/07/2025
Size:
½” BSP male inlet/outlet
Marking:
Hyco, serial number, model, manufacturer, address, contact No, product code and other technical information side of unit.
Installation Requirements:
R001
Model:
IN44T, IN60T, IN96T, IN44 & IN60.
Approval Holder:
Hyco Manufacturing Ltd
Company Name
Hyco Manufacturing Ltd
Address
California Drive, Castleford, West Yorkshire
Postcode
WF10 5QH

View All Listings by this Company
Manufacturer:
Hyco Manufacturing Ltd
Company Name
Hyco Manufacturing Ltd
Address
California Drive, Castleford, West Yorkshire
Postcode
WF10 5QH

View All Listings by this Company

Print This Approval


#240202708

Wall mounted electric instantaneous water heater. The inlet incorporates a plastic flow sensor with strainer. Maximum working pressure 6.0 Bar Maximum operating temperature 55.0°C

Section:
1360 Heaters
Section Subtitle:
Electric instantaneous, mains fed, closed outlet. Heat retained in instantaneous water heaters will cause expansion of water after closure of draw-off taps and valves. Provision for expansion of water must be made to accommodate excess pressure within the system. Particular care is required where check valves are positioned, or loose jumper valves are thought to be upstream of the heater.
WRAS Approval Number:
240202708
Expiry date:
28/02/2029
Size:
½” BSP (M).
Marking:
Water Waiter, Genius zero carbon solutions Ltd, model, max pressure and other technical information on label.
Installation Requirements:
R001
Model:
WW131070
Approval Holder:
Genius Zero Carbon Solutions Ltd
Company Name
Genius Zero Carbon Solutions Ltd
Address
21 CHURCH ROAD, PARKSTONE, POOLE, ENGLAND, BH14 8UF

View All Listings by this Company

Print This Approval


Show Per Page
5102050Show All

Back To Directory Sections

Page of 1

We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.