Range of bedpan washing & disinfection machines. The flow is controlled by a solenoid valve and discharged via a type `AB` airgap (verified by test - suitable for backflow protection against fluid category 5). Maximum working pressure - See models Maximum operating temperature - 90 °C
Range of commercial washing machines with flow controlled by solenoid valves and discharged via type AB air gap assembly (verified by test - suitable for backflow protection against fluid category 5). The inlets incorporate approved check valve cartridges, however, the complete product has not been fully tested to demonstrate it provides backflow protection Maximum working pressure 5 Bar. Maximum operating temperature 60°C.
Range of in-line electrolytic scale inhibitors with copper bodies, for use with copper pipe manufactured to BS EN 1057 Maximum working pressure 20.0 bar. Cold water use only
Range of inline water conditioners with stainless steel bodies and catalytic alloy core. Maximum working pressure 16.0 bar. Maximum operating temperature 100°C.
‘G5 C’ command centre providing chilled (filtered) water via an electronically controlled tap (not supplied). Flow is controlled via a combination of solenoid valves and electronic pumps to the outlets. The products are supplied with a filter cartridge. The inlet to the command centre incorporates two approved check valve cartridges, however, the complete product has not been fully tested to demonstrate it provides backflow protection. Maximum inlet supply pressure 5.0 bar. Cold water use only.
Page 1472 of 2300
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.