Range of multistage centrifugal pumps with stainless steel impellers, intermediate chambers, shaft and outer sleeve.
The DPV(M/S) models and DPV(S) models can also incorporate an approved check valve cartridge; however, the complete product has not been fully tested to demonstrate it provides backflow protection.
Maximum working pressures:
Existing models:
DPV models 10.0 bar,
DPVM models with an oval flange or VME models with integral check valve 16.0 bar,
All other DPVM models 25.0 bar.
DPV(S) models with an oval flange or DPV(S)(E) models with integral check valve 16.0 bar,
All other DPV(S) models and DPH(S)I models 25.0 bar.
Maximum operating temperatures:
DPHM, DPVE and DPVME models with integral check valve 60°C, all other model variants 100°C.
- Section:
- 1610 Pumps
- Section Subtitle:
- Wholesome water use.
- WRAS Approval Number:
- 250302723
- Basis of Compliance:
- Tested to regulators Specification Test Code Sheets
- Size:
- DPHM 2/4/6 B:
1¼” BSP (F) inlet x 1” BSP (F) outlet.
DPV(M/S)(F/E/V/T) 2/4/6 B:
Oval flange: DN25, DN32.
Round flange: DN25, DN32.
External threaded: 1½” BSP (M),
Victaulic: DN32 and
Tri-clamp: DN32.
DPV(S) (F/E/V/T) 10 B/15 B/15 C:
Oval flange: DN40, DN50.
Round flange: DN40, DN50.
External threaded: 1½” BSP (M),
Victaulic: DN50 and
Tri-clamp: DN50.
DPV(S)F 25/40/60/85/125 B:
Round flange: DN65, DN80, DN100, DN125.
DPH(S)I 2/4/6 B:
1¼” BSP or NPT (F).
DPH(S)I 10/15 B/C:
2” BSP or NPT (F).
- Marking:
- DPVF & logo, model name, PN, WRAS and technical information on adhesive label on body.
- Installation Requirements:
- R001 R415
- Expiry date:
- 31/03/2030
- Model:
-
DPHM x yy B.
Where:
x = flow rate m³/h (2, 4 or 6).
yy = no. of stages
ranges 1-6 stages.
-------------------------------------
DPV(M/S)(F/E/V/T) x yy B/C
Where:
V = Vertically oriented (AISI 304) with coupling.
VS = Vertically oriented (AISI 316) with coupling.
No indication (V/VS only) = oval flange.
F (VF/VSF) = round flange.
E (VE) = external thread.
V (VV/VSV) = Victaulic.
T (VT/VST) = Triclamp.
x = flow rate m³/h (2, 4, 6, 10, 15).
yy = no. of stages
DPV(M/S)(F/E/V/T)……2 B 1-30 stages.
DPV(M/S)(F/E/V/T)……4/6 B 1-26 stages.
DPV(S)(F/E/V/T)……10 B 1-21 stages.
DPV(S)(F/E/V/T)……15 B/C 1-17 stages.
--------------------------------------
DPV(S) F xx yy B.
Where:
V = Vertically oriented (AISI 304) with coupling.
VS = Vertically oriented (AISI 316) with coupling.
F (VF/VSF) = round flange.
x = flow rate m³/h (25, 40, 60, 90 or 125).
yy = no. of stages
……25 B 1-12 stages.
……40/60 B 1-10 stages.
……90 B 1-6 stages.
……125 B 1-4 stages.
--------------------------------------
DPHI x yy = Vertically oriented (AISI 304).
DPHSI x yy = Vertically oriented (AISI 316).
Where:
I = Inner thread connection.
x = flow rate m³/h (2, 4, 6, 10 or 15).
yy = no. of stages
DPH(S)I 2/4/6 B 1-14 stages.
DPH(S)I 10 B/15 B/15 C 1-8 stages.
- Approval Holder:
- Duijvelaar Pompen B.V.
Company Name
Duijvelaar Pompen B.V.
Address
Kalkovenweg 13
2401 LJ Alpen aan den Rijn
Phone
0031 0172 488388
View All Listings by this Company