Range of indirect heat interface units with copper brazed stainless-steel heat exchangers, providing heating and instantaneous hot water. The products incorporate an expansion vessel on the cold-water supply to the plate heat exchanger and a safety relief valve on the space heating circuit set @ 3.0 bar. The domestic hot water and space heating circuit are both fitted with drain valves incorporating cover caps. Maximum working pressures: Domestic hot water 10.0 bar. Space Heating 2.5 bar. District Heating 3.0 bar. Maximum operating temperature 85˚C.
Indirect heat interface unit with copper brazed, stainless-steel heat exchangers, providing heating and instantaneous hot water. The product incorporates an expansion vessel on the cold-water supply to the plate heat exchanger and a safety relief valve on the heating circuit set @ 2.5 bar. The DHW and heating circuits are both fitted with drain valves incorporating cover caps. Maximum working pressure 16 Bar (Primary), 10 Bar (DHW) & 3 Bar (Heating) Maximum operating temperature 95°C
Page of 1
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.