Heat Exchangers

Section Code 1350 :

Back To Directory Sections

#2201323

Domestic hot water heat recovery unit incorporating a stainless-steel plate heat exchanger and cylinder. Maximum working pressure 3.0 bar. Maximum operating temperature 60°C.

Section:
1350 Heat Exchangers
WRAS Approval Number:
2201323
Expiry date:
31/01/2027
Size:
15mm copper tail
Marking:
Baxi, Assure FGHR1, date of manufacturer (YYWW) on body.
Installation Requirements:
R001 R140
Model:
Baxi Assure FGHR1
Manufacturer:
Baxi Heating UK Limited
Company Name
Baxi Heating UK Limited
Address
Brooks House, Coventry Road, Warwick
Postcode
CV34 3LL

View All Listings by this Company

Print This Approval


#2204319

Range of plate heat exchanger with stainless steel bodies. Maximum working pressure10 bar. Maximum operating temperature 100°C.

Section:
1350 Heat Exchangers
WRAS Approval Number:
2204319
Expiry date:
30/04/2027
Size:
½”BSP(M) secondary x ¾”BSP(M) primary Ø 16mm holes on inlets and outlets
Marking:
G20 Engineering logo, model number, production date WW/YY etched on body
Installation Requirements:
R001
Model:
Plate heat exchanger – Type PEP15440A01 (with insert M5) PEP15440A01-20 PEP15440A01-18 PEP15440A01-16 PEP15440A01-14 PEP15440A01-12 PEP15440A01-10 Plate heat exchanger – Type PEP15440B01 (with 2 G ½’ fitting and 2 G ¾’ fitting) PEP15440B01-20 PEP15440B01-18 PEP15440B01-16 PEP15440B01-14 PEP15440B01-12 PEP15440B01-10
Factor:
G20 ENGINEERING s.r.l.
Company Name
G20 ENGINEERING s.r.l.
Address
Localita Campogrande 13- 29013 Carpaneto P.no (PC)
Country
Italy

View All Listings by this Company

Print This Approval


#2204326

‘POD’ range of indirect and direct heat interface units providing space heating and instantaneous hot water. The heat transfer is generated via plate heat exchangers. The domestic hot water (DHW) circuit incorporates an adjustable temperature mixing valve. The indirect models incorporate an expansion vessel (on the CW inlet of the DHW circuit) and a pressure relief valve set at 3.0 bar (on the space heating circuit). The indirect models only are supplied with a temporary filling loop, which comprises of a stainless steel braided EPDM lined flexible hose assembly and a lever operated spherical valve for connection to the primary circuit. The angled cold water inlet incorporates an isolation valve and a branch to connect to the filling loop, which includes a double check valve assembly (verified by test, suitable for backflow protection against Fluid Category 3). Maximum working pressure for indirect units: Primary circuit: 16.0 bar. Space heating: 2.5 bar. Secondary circuit (DHW): 10.0 bar. Maximum working pressure for direct units: Primary circuit: 10.0 bar. Space heating: 10.0 bar. Secondary circuit (DHW): 10.0 bar. Maximum operating temperature for domestic hot water 65°C. Maximum operating temperature for central heating and primary circuit 85°C.

Section:
1350 Heat Exchangers
WRAS Approval Number:
2204326
Expiry date:
30/04/2027
Size:
22mm copper pipe connection.
Marking:
Ideal Heating badge and model on adhesive label on front casing. Manufacturer, serial number, model number, pressure rating and other technical information on data label within appliance.
Installation Requirements:
R001 R140 R360
Model:
POD range of indirect (i prefix) and direct (d prefix) HIU: i305, i405, i505, i605, i705, d30, d40, d50, d60. All models can have the following suffixes to denote the inclusion of a heat meter: HWM for a hard wired MBUS and WLM for a wireless MBUS.
Manufacturer:
Ideal Heating.Limited
Company Name
Ideal Heating.Limited
Address
Po Box 103 National Avenue Kingston Upon Hull Humberside
Postcode
HU5 4JN

View All Listings by this Company

Print This Approval


#2204062

Range of stainless-steel plate heat exchangers. Maximum operating pressures - primary circuit: 3.0 bar, secondary circuit (DHW): 10.0.bar. Maximum working temperature 80°C.

Section:
1350 Heat Exchangers
WRAS Approval Number:
2204062
Expiry date:
30/04/2027
Size:
Ø 15.6mm holes on inlets and outlets
Marking:
Condevo, model name, date of manufacture (DDMMYY) on adhesive label on body
Installation Requirements:
R001
Model:
Models added January 2024: Type ‘H’ range of Heat Exchangers: PPAAFHBCDE Where: PP = Product plates, AA = Number of plates in multiples of 2, 8 plates and also ranging from 36 to 44 plates, FH = Model of plates and flow, B = Material type of exchange plates - 4 = AISI304L or 6 = AISI316L, C = Coupling plate - T or R to denote hole distance option, DE = Configuration - position of studs and/or position of label (indicates configuration: progressive) - can be any 2 digit number or alphanumeric combination.
Manufacturer:
Condevo SpA
Company Name
Condevo SpA
Address
Via Luna, Z.A. 26866 Marudo (LO) Italy

View All Listings by this Company

Print This Approval


#2206361

Range of heat exchangers connected to copper waste pipe, Where the waste is discharged down a “rotator” into a copper waste pipe, and potable water is returned to the shower/heating device via a copper double walled jacket around the copper waste pipe. Maximum working pressure 8.0 bar. Maximum operating temperature 60°C

Section:
1350 Heat Exchangers
WRAS Approval Number:
2206361
Expiry date:
30/06/2027
Size:
½” BSP (F)
Marking:
Manufacturer ( Builidng Product Distribution) Manufacturer address Type Category BPD Ltd Serial No. Model & other information on Adhesive label.
Installation Requirements:
R001
Model:
Showersave: QB1-21C QB1-16C QB1-12C QB1-21 Cyclone QB1-21 QB1-16 QB1-12 QB1-21D QB1-21D HE
Factor:
BPD Limited
Company Name
BPD Limited
Address

View All Listings by this Company

Print This Approval



Back To Directory Sections

Page 8 of 11

We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.