Range of UV disinfection units with stainless steel bodies. Maximum working pressure 10.0 bar. Cold water use only.
Range of UV disinfection units with stainless steel bodies and quartz tube. Maximum working pressure 10.0 bar. Cold water use only.
Range of UV disinfection units with stainless steel bodies. Maximum working pressure 10.0 bar. Cold water use only.
'ANUBIT HB-1000'. Factory applied, black coloured bitumen coating. Apply as per manufacturer's TDS 'AE-TDS-023-2021', dated '02.08.2024'. Please note that use of a thinner isn't covered by the scope of this approval. Cure for 40 minutes@30°C. For use with water up to 23°C. This material is only approved for the curing conditions that appear on the approval. If the cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Tuffkote Bituminous Aluminium'. Factory applied, grey coloured, two-component crude oil bitumen coating. Mix in a 17.1:2.9 volume ratio and apply as per manufacturer's data sheet 'SPL/PMG/2019100166', 'Rev 2', dated '04/2024'. Cure for 7 days@30°C. For use with water up to 23°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the materials are not covered by the scope of the approval.
Page 969 of 1315
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.