Section Code 5021 : Petroleum or asphaltic bitumen, NOT coal tar bitumen. Materials containing petroleum or asphaltic bitumen are not approved for use on water-retaining structures with large surface:volume ratio such as lining of pipes, cisterns or water storage tanks in contact with wholesome water, but may be acceptable for use where there is only a small surface area in contact with the water – e.g. taps, valves and pipe connectors.
Back To Directory Sections'Tuffkote Bituminous coating'. Factory applied, grey coloured, two-component crude oil bitumen coating. Mix in a 17.1:2.9 volume ratio and apply as per manufacturer's data sheet 'SPL/PMG/2019100166', 'Rev 2', dated '04/2024'. Cure for 7 days@30°C. For use with water up to 23°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the materials are not covered by the scope of the approval.
Page 3 of 3
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.