Thermaq Ltd Approvals


#1909103

THERMAQ PROLITE range of stainless steel direct and indirect, direct (solar) and indirect (solar) hot water storage cylinders. The secondary circuit is factory fitted with a temperature and pressure relief valve set at 7.0 bar and 90˚C. A safety kit (manifold) consisting of a single check valve cartridge (verified by test, suitable for backflow protection against Fluid Category 2), strainer, an expansion relief valve set at 6.0 bar and pressure reducing valve set at 3.0 bar. A tundish and expansion vessel is also supplied. Maximum working pressure and temperature secondary circuit 5.5 bar @65°C Maximum operating pressure and temperature primary circuit 6.0 bar @80°C

Section:
1890 Unvented Heating Apparatus
WRAS Approval Number:
1909103
Expiry date:
30/09/2024
Note:
Not supplied with a temporary filling loop. A filling loop must be installed with the appropriate backflow prevention device in accordance with clause G24.2, Guidance to the Water Supply (Water Fittings) Regulations 1999. Expansion vessels should be installed in the vertical orientation, and located so as to minimise the length of any connecting pipework.
Size:
90 litre, 120 litre, 150 litre, 180 litre, 210 litre, 250 litre, 300 litre,
Marking:
PROLITE SS ON CYLINDER THERMAQ PROLITE, MODEL, PRESSURE, CAPACITY & TECHNICAL INFORMATION ON ADHESIVE LABEL ON BODY
Installation Requirements:
R001 R360
Proviso:
WRAS Approval - Solar heating system components. “Compliance with the relevant requirements of the Water Supply (Water Fittings) Regulations 1999 has been assessed for this product only as a component of a heating system. If it is to be installed a s part of a system using solar energy or ground - or air - source heat pumps for pre-heating water which is to be used as domestic hot water, the Water Fittings Regulation place a legal duty on the installer and user to ensure that the installation and operation of the complete system prevents contamination of domestic hot water by Legionella bacteria, which can grow in water stored at temperatures between 20˚C and 45˚C. Where disinfection by heating is relied on to meet this obligation, information on minimum conditions for thermal disinfection of legionella bacteria can be found on the WRAS website - www.wras.co.uk
Model:
TTPMVD-0090LFC THERMAQ PROLITE SS 90 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTPMVD-0120LFB THERMAQ PROLITE SS 120 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTPMVD-0150LFB THERMAQ PROLITE SS 150 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTPMVD-0180LFB THERMAQ PROLITE SS 180 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTPMVD-0210LFC THERMAQ PROLITE SS 210 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTPMVD-0250LFC THERMAQ PROLITE SS 250 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTPMVD-0300LFC THERMAQ PROLITE SS 300 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTPMVI-0090LFC THERMAQ PROLITE SS 90 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTPMVI-0120LFB THERMAQ PROLITE SS 120 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTPMVI-0150LFB THERMAQ PROLITE SS 150 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTPMVI-0180LFB THERMAQ PROLITE SS 180 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTPMVI-0210LFC THERMAQ PROLITE SS 210 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTPMVI-0250LFC THERMAQ PROLITE SS 250 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTPMVI-0300LFC THERMAQ PROLITE SS 300 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER.
Factor:
Thermaq Ltd
Company Name
Thermaq Ltd
Address
Sandbeds Trading Estate Dewsbury Road Ossett
Postcode
WF5 9ND
General Email
steve.woollas@rmcylinders.com

View All Listings by this Company

Print This Approval


#1909104

THERMAQ EVOCYL range of stainless steel direct and indirect, direct (solar) and indirect (solar) hot water storage cylinders. The secondary circuit is factory fitted with a temperature and pressure relief valve set at 7.0 bar and 90˚C. A safety kit (manifold) consisting of a single check valve cartridge (verified by test, suitable for backflow protection against Fluid Category 2), strainer, an expansion relief valve set at 6.0 bar and pressure reducing valve set at 3.0 bar. A tundish and expansion vessel is also supplied. Maximum working pressure and temperature secondary circuit 5.5 bar @65°C Maximum operating pressure and temperature primary circuit 6.0 bar @80°C

Section:
1890 Unvented Heating Apparatus
WRAS Approval Number:
1909104
Expiry date:
30/09/2024
Note:
Not supplied with a temporary filling loop. A filling loop must be installed with the appropriate backflow prevention device in accordance with clause G24.2, Guidance to the Water Supply (Water Fittings) Regulations 1999. Expansion vessels should be installed in the vertical orientation, and located so as to minimise the length of any connecting pipework.
Size:
90 litre, 120 litre, 150 litre, 180 litre, 210 litre, 250 litre, 300 litre, 350 litre, 400 litre, 450 litre, 500 litre.
Marking:
THERMAQ EVOCYL ON CYLINDER THERMAQ EVOCYL, MODEL, PRESSURE, CAPACITY & TECHNICAL INFORMATION ON ADHESIVE LABEL ON BODY
Installation Requirements:
R001 R360
Proviso:
WRAS Approval - Solar heating system components. “Compliance with the relevant requirements of the Water Supply (Water Fittings) Regulations 1999 has been assessed for this product only as a component of a heating system. If it is to be installed a s part of a system using solar energy or ground - or air - source heat pumps for pre-heating water which is to be used as domestic hot water, the Water Fittings Regulation place a legal duty on the installer and user to ensure that the installation and operation of the complete system prevents contamination of domestic hot water by Legionella bacteria, which can grow in water stored at temperatures between 20˚C and 45˚C. Where disinfection by heating is relied on to meet this obligation, information on minimum conditions for thermal disinfection of legionella bacteria can be found on the WRAS website - www.wras.co.uk
Model:
TTEMVD-0090LFC -THERMAQ EVOCYL 90 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVD-0120LFB -THERMAQ EVOCYL 120 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVD-0150LFB -THERMAQ EVOCYL 150 DIRECT UNVENTED HOT WATER STORAGE CYLINDER TTEMVD-0180LFB -THERMAQ EVOCYL 180 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVD-0210LFC -THERMAQ EVOCYL 210 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVD-0250LFC -THERMAQ EVOCYL 250 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVD-0300LFC -THERMAQ EVOCYL 300 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVD-0350LFC -THERMAQ EVOCYL 350 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVD-0400LFC -THERMAQ EVOCYL 400 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVD-0450LFC -THERMAQ EVOCYL 450 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVD-0500LFC -THERMAQ EVOCYL 500 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVI-0090LFC -THERMAQ EVOCYL 90 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVI-0120LFB -THERMAQ EVOCYL 120 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVI-0150LFB -THERMAQ EVOCYL 150 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVI-0180LFB -THERMAQ EVOCYL 180 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVI-0210LFC -THERMAQ EVOCYL 210 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVI-0250LFC -THERMAQ EVOCYL 250 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVI-0300LFC -THERMAQ EVOCYL 300 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVI-0350LFC -THERMAQ EVOCYL 350 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVI-0400LFC -THERMAQ EVOCYL 400 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVI-0450LFC -THERMAQ EVOCYL 450 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTEMVI-0500LFC -THERMAQ EVOCYL 500 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER TTEMVE-0150LFB -THERMAQ EVOCYL 150 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTEMVE-0180LFB -THERMAQ EVOCYL 180 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTEMVE-0210LFC -THERMAQ EVOCYL 210 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTEMVE-0250LFC -THERMAQ EVOCYL 250 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTEMVE-0300LFC -THERMAQ EVOCYL 300 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTEMVE-0350LFC -THERMAQ EVOCYL 350 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTEMVE-0400LFC -THERMAQ EVOCYL 400 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTEMVE-0450LFC -THERMAQ EVOCYL 450 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTEMVE-0500LFC -THERMAQ EVOCYL 500 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTEMVS-0150LFB -THERMAQ EVOCYL 150 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER. TTEMVS-0180LFB -THERMAQ EVOCYL 180 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER. TTEMVS-0210LFC -THERMAQ EVOCYL 210 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER. TTEMVS-0250LFC -THERMAQ EVOCYL 250 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER. TTEMVS-0300LFC -THERMAQ EVOCYL 300 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER. TTEMVS-0350LFC -THERMAQ EVOCYL 350 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER. TTEMVS-0400LFC -THERMAQ EVOCYL 400 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER. TTEMVS-0450LFC -THERMAQ EVOCYL 450 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER. TTEMVS-0500LFC -THERMAQ EVOCYL 500 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER
Factor:
Thermaq Ltd
Company Name
Thermaq Ltd
Address
Sandbeds Trading Estate Dewsbury Road Ossett
Postcode
WF5 9ND
General Email
steve.woollas@rmcylinders.com

View All Listings by this Company

Print This Approval


#1909105

THERMAQ UNICYL range of stainless steel direct and indirect, direct (solar) and indirect (solar) hot water storage cylinders. The secondary circuit is factory fitted with a temperature and pressure relief valve set at 7.0 bar and 90˚C. A safety kit (manifold) consisting of a single check valve cartridge (verified by test, suitable for backflow protection against Fluid Category 2), strainer, an expansion relief valve set at 6.0 bar and pressure reducing valve set at 3.0 bar. A tundish and expansion vessel is also supplied. Maximum working pressure and temperature secondary circuit 5.5 bar @65°C Maximum operating pressure and temperature primary circuit 6.0 bar @80°C

Section:
1890 Unvented Heating Apparatus
WRAS Approval Number:
1909105
Expiry date:
30/09/2024
Note:
Not supplied with a temporary filling loop. A filling loop must be installed with the appropriate backflow prevention device in accordance with clause G24.2, Guidance to the Water Supply (Water Fittings) Regulations 1999. Expansion vessels should be installed in the vertical orientation, and located so as to minimise the length of any connecting pipework.
Size:
90 litre, 120 litre, 150 litre, 180 litre, 210 litre, 250 litre, 300 litre,
Marking:
THERMAQ UNICYL ON CYLINDER THERMAQ UNICYL, MODEL, PRESSURE, CAPACITY & TECHNICAL INFORMATION ON ADHESIVE LABEL ON BODY
Installation Requirements:
R001 R360
Proviso:
WRAS Approval - Solar heating system components. “Compliance with the relevant requirements of the Water Supply (Water Fittings) Regulations 1999 has been assessed for this product only as a component of a heating system. If it is to be installed a s part of a system using solar energy or ground - or air - source heat pumps for pre-heating water which is to be used as domestic hot water, the Water Fittings Regulation place a legal duty on the installer and user to ensure that the installation and operation of the complete system prevents contamination of domestic hot water by Legionella bacteria, which can grow in water stored at temperatures between 20˚C and 45˚C. Where disinfection by heating is relied on to meet this obligation, information on minimum conditions for thermal disinfection of legionella bacteria can be found on the WRAS website - www.wras.co.uk
Model:
TTUMVD-0090LFC -THERMAQ UNICYL 90 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVD-0120LFB -THERMAQ UNICYL 120 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVD-0150LFB -THERMAQ UNICYL 150 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVD-0180LFB -THERMAQ UNICYL 180 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVD-0210LFC -THERMAQ UNICYL 210 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVD-0250LFC -THERMAQ UNICYL 250 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVD-0300LFC -THERMAQ UNICYL 300 DIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVI-0090LFC -THERMAQ UNICYL 90 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVI-0120LFB -THERMAQ UNICYL 120 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVI-0150LFB -THERMAQ UNICYL 150 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVI-0180LFB -THERMAQ UNICYL 180 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVI-0210LFC -THERMAQ UNICYL 210 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVI-0250LFC -THERMAQ UNICYL 250 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVI-0300LFC -THERMAQ UNICYL 300 INDIRECT UNVENTED HOT WATER STORAGE CYLINDER. TTUMVE-0150LFB -THERMAQ UNICYL 150 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTUMVE-0180LFB -THERMAQ UNICYL 180 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTUMVE-0210LFC -THERMAQ UNICYL 210 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTUMVE-0250LFC -THERMAQ UNICYL 250 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTUMVE-0300LFC -THERMAQ UNICYL 300 DIRECT SOLAR UNVENTED HOT WATER STORAGE CYLINDER. TTUMVS-0150LFB -THERMAQ UNICYL 150 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER. TTUMVS-0180LFB -THERMAQ UNICYL 180 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER. TTUMVS-0210LFC -THERMAQ UNICYL 210 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER. TTUMVS-0250LFC -THERMAQ UNICYL 250 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER. TTUMVS-0300LFC -THERMAQ UNICYL 300 INDIRECT SOLAR TWIN UNVENTED HOT WATER STORAGE CYLINDER.
Factor:
Thermaq Ltd
Company Name
Thermaq Ltd
Address
Sandbeds Trading Estate Dewsbury Road Ossett
Postcode
WF5 9ND
General Email
steve.woollas@rmcylinders.com

View All Listings by this Company

Print This Approval


Show Per Page
5102050Show All

Back To Directory Sections

Page of 1

We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.